95
09 Set (Reflex)
The
Set
output is activated when the assigned groups on the system are set. This output is a
Reflex
output
and follows the set and unset status of the groups.
10 Engineer (Reflex)
The
Engineer
output is activated while the engineer mode is being accessed.
11 Spare (Latch)
The
Spare
output has function: it is used to designate outputs that are not being used on the system.
12 Ready (Reflex)
The
Ready
output is active when all zones in the system (group) are closed. This output activates in both the
unset and set conditions.
13 Security (Latch)
The
Security
output is activated whenever a
Security
zone is activated. The output is not subject the
Rearm
parameter: it latches on and remains active until a valid code (type 2 or above) is entered.
14 AC Fail (Reflex)
The
AC Fail
output indicates the status of the a.c. (mains) power supply. The output activates when the a.c.
supply fails or an
AC Fail
zone is activated. The output is reset when the a.c. supply is restored or the
AC
Fail
zone is closed. The activation is delayed subject to the time entered in the
20=Power Delay
parameter.
15 Battery Low (Reflex)
The
Battery Low
output activates whenever the control unit stand-by battery falls below 10.5V or a
Battery
Low
zone is activated. The output is restored when the voltage rises above 10.5V or the
Battery Low
zone
is closed.
16 Fire (Latch)
The
Fire
output is activated whenever a
Fire
zone is activated. The output is not subject to the
Rearm
parameter: it latches on and remains active until a valid code (type 2 or above) is entered.
17 Horn (Latch)
The
Horn
output is a general alarm output and is activated by most zone types in both the local and full alarm
modes. For example, a
Fire
zone activation causes the
Horn
output to pulse on and off – on for 0.5 seconds,
off for 0.1 seconds. The
Horn
output is subject to the
Bell Time, Bell Delay and No. Rearm
parameters.
53 - Program Outputs (cont’d)
Summary of Contents for 3-144
Page 1: ...Honeywell Security Galaxy 3 48C 3 144 3 144C 3 520 3 520C Programming Manual ...
Page 2: ......
Page 8: ...Galaxy 3 Series Programming Manual 2 ...
Page 30: ...Galaxy 3 Series Programming Manual 24 ...
Page 184: ...Galaxy 3 Series Programming Manual 178 ...
Page 188: ...Galaxy 3 Series Programming Manual A 4 ...
Page 202: ...Galaxy 3 Series Programming Manual C 2 ...
Page 212: ...2 Galaxy 3 Series Programming Manual ...