Galaxy 3 Series Programming Manual
62
35 = Fail to Set
This parameter determines the period of time that a zone must remain open, following the start of the setting
procedure, before the
Fail Set
outputs activate. The programmable range is
0–999
seconds; the default is
360
.
NOTE:
The
Fail to Set
countdown time begins as soon as the setting procedure is started.
NOTE:
The
Fail to Set
time should be at a minimum 5 seconds longer than the
Exit Time
(option 51.04),
to allow for the setting period to expire.
This parameter can be assigned a different value for each group.
36 = Battery Size
Enter the size of the standby battery on the control Panel PSU. The programmable range is
0–99
Ah; the
default is
0
.
37 = Standby Time
Enter the value (in hours) that the system is required to run on standby battery if there is a mains fail. The
programmable range is
0–99
hours; the default is
0
.
The Control Panel PSU calculates the battery run time from the programmed
Battery Size
(parameter
36
)
and the load current. If the programmed
Standby Time
exceeds the calculated battery run time, a
STANDBY TIME LOW
message is displayed on the keypad on attempting to exit engineer mode. Exiting
engineer mode is prevented until a
Standby Time
that is less than the calculated battery time is entered or a
larger battery is installed in the system and the new battery size is entered in the
Battery Size
parameter.
To view the latest battery
Standby Time
refer to Option
61.1.4=Diagnostics.Latest.PSU Comms.
NOTE:
The calculated battery run time has a 10% safety margin built in.
38 = ATM Delay
This parameter determines the period of time before the selected
ATM
zone type is omitted following the
entry of one of the
ATM
codes. The programmable range is
0–30
minutes; the default
ATM Delay
is
5
.
39 = ATM Timeout
This parameter determines the period of time that the selected
ATM
zone type is omitted following the entry
of one of the
ATM
codes. The programmable range is
1–90
minutes; the default
ATM Timeout
is
30
.
51 - Parameters (cont’d)
Summary of Contents for 3-144
Page 1: ...Honeywell Security Galaxy 3 48C 3 144 3 144C 3 520 3 520C Programming Manual ...
Page 2: ......
Page 8: ...Galaxy 3 Series Programming Manual 2 ...
Page 30: ...Galaxy 3 Series Programming Manual 24 ...
Page 184: ...Galaxy 3 Series Programming Manual 178 ...
Page 188: ...Galaxy 3 Series Programming Manual A 4 ...
Page 202: ...Galaxy 3 Series Programming Manual C 2 ...
Page 212: ...2 Galaxy 3 Series Programming Manual ...