Galaxy 3 Series Programming Manual
173
Option 67 – Remote Reset
The
Remote Reset
option allows a user to perform an engineer reset authorized by the Alarm Receiving
Centre (ARC). In the event of an alarm that requires an engineer reset, the keypad displays a number, which,
when quoted to the ARC is decoded and exchanged for a new number. When this new number is entered it
resets the Galaxy panel. Entering the engineer code also resets the Galaxy panel.
NOTE:
The alarm conditions that require to be reset remotely must have the appropriate
System Reset
,
Tamper Reset
or
PA Reset
parameters programmed for engineer reset (
type 3.7
).
Each alarm activation generates a random number, therefore, the number required to reset the panel changes
each activation. As ARCs have different decoding equipment, the appropriate reset system must be selected
from the following
Remote Mode
options:
0 = OFF
(default).
1 = SMS
- Southern Monitoring Service (4 digits).
2 = Technistore
(5 digits) - requires a four digit local modifier (000 - 255) to be assigned.
3 = Microtech
(6 digits) - requires a four digit local modifier (0000 - 9999) to be assigned.
NOTE
: The local modifier for the Technistore or Microtech reset modes must be assigned after discussion
with the ARC.
67 - Remote Reset
Summary of Contents for 3-144
Page 1: ...Honeywell Security Galaxy 3 48C 3 144 3 144C 3 520 3 520C Programming Manual ...
Page 2: ......
Page 8: ...Galaxy 3 Series Programming Manual 2 ...
Page 30: ...Galaxy 3 Series Programming Manual 24 ...
Page 184: ...Galaxy 3 Series Programming Manual 178 ...
Page 188: ...Galaxy 3 Series Programming Manual A 4 ...
Page 202: ...Galaxy 3 Series Programming Manual C 2 ...
Page 212: ...2 Galaxy 3 Series Programming Manual ...