42
“d” Function
Func.
Code
Name
Description
Run
Mode
Edit
Units
D080
Trip counter
Number of trip events,
Range is 0. to 65530
−
events
D081
Trip monitor 1
−
−
D082
Trip monitor 2
−
−
D083
Trip monitor 3
−
−
d084
Trip monitor 4
−
−
d085
Trip monitor 5
−
−
d086
Trip monitor 6
Displays trip event information:
•
Error
code
•
Output frequency at trip point
•
Motor current at trip point
•
DC bus voltage at trip point
•
Cumulative inverter operation
time at trip point
•
Cumulative power-ON time at
trip point
−
−
d090
Warning monitor
Displays the warning code
−
−
D102
DC bus voltage monitor
Voltage of inverter internal DC bus,
Range is 0.0 to 999.9
−
V
d103
BRD load ratio monitor
Usage ratio of integrated brake
chopper, range is 0.0~100.0%
−
%
D104
Electronic thermal monitor
Accumulated value of electronic
thermal detection, range is from
0.0~100.0%
−
%
Main Profile Parameters
NOTE
:. Mark “
9
” in b031=10 shows the accessible parameters when b031 is set “10”, high
level access.
“F” Function
Defaults
Func.
Code
Name
Description
Run
Mode
Edit
Initial data
Units
F001
Output frequency setting
Standard default target frequency
that determines constant motor
speed, range is 0.0 / start
frequency to maximum frequency
(A004)
9
0.0 Hz
F002
Acceleration time (1)
9
10.0 sec.
F202
Acceleration time (1),
2
nd
motor
Standard default acceleration,
range is 0.01 to 3600 sec.
9
10.0 sec.
F003
Deceleration time (1)
9
10.0 sec.
F203
Deceleration time (1),
2
nd
motor
Standard default deceleration,
range is 0.01 to 3600 sec.
9
10.0 sec.
F004
Keypad RUN key routing
Two options; select codes:
00
…
Forward
01
…
Reverse
U