62
“C” Function
Defaults
Func.
Code
Name
Description
Run
Mode
Edit
Initial data
Units
C076
Communication error
select
Selects inverter response to
communications error.
Five options:
00
…
Trip
01
…
Decelerate to a stop and trip
02
…
Disable
03
…
Free run stop (coasting)
04
…
Decelerates to a stop
U
02
−
C077
Communication error
time-out
Sets the communications watchdog
timer period.
Range is 0.00 to 99.99 sec
0.0 = disabled
U
0.00 sec.
C078
Communication wait time
Time the inverter waits after
receiving a message before it
transmits.
Range is 0. to 1000. ms
U
0. msec.
C081
O input span calibration
Scale factor between the external
frequency command on terminals
L–O (voltage input) and the
frequency output,
range is 0.0 to 200%
9
100.0 %
C082
OI input span calibration
Scale factor between the external
frequency command on terminals
L–OI (voltage input) and the
frequency output,
range is 0.0 to 200%
9
100.0 %
C085
Thermistor input (PTC)
span calibration
Scale factor of PTC input.
Range is 0.0 to 200%
9
100.0 %
C091
Debug mode enable
Displays debug parameters.
Two option codes:
00
…
Disable
01
…
Enable
<Do not set>
(for factory use)
9
00
−
C096
Communication selection
00
…
Modbus-RTU
01
…
EzCOM
02
…
EzCOM<administrator>
U
00
−
C098
EzCOM start adr. of master 01-08
U
01
−
C099
EzCOM end adr. of master 01-08
U
01
−
C100
EzCOM starting trigger
00
…
Input terminal
01
…
Always
U
00
−
C101
Up/Down memory mode
selection
Controls speed setpoint for the
inverter after power cycle.
Two option codes:
00
…
Clear last frequency (return to
default frequency
F001
)
01
…
Keep last frequency adjusted
by UP/DWN
U
00
−