58
“b” Function
Defaults
Func.
Code
Name
Description
Run
Mode
Edit
Initial data Units
B134
Decel. overvolt. Suppress
integral time
Integration time when b130=01.
Range is: 0.00 to 150.0
9
1.0 sec.
b145
GS input mode
Two option codes:
00
…
No trip (Hardware shutoff only)
01
…
Trip
U
00
−
b150
Display ex.operator connected
When an external operator is
connected via RS-422 port, the
built-in display is locked and shows
only one "d" parameter configured
in:
d001
~
d030
U
001
−
b160
1st parameter of Dual Monitor
U
001
−
b161
2nd parameter of Dual Monitor
Set any two "d" parameters in b160
and b161, then they can be
monitored in d050. The two
parameters are switched by
up/down keys.
Set range:
d001
~
d030
U
002
−
b163
Frequency set in monitoring
Two option codes:
00
…
Freq. set disabled
01
…
Freq. set enabled
9
00
−
b164
Automatic return to the initial
display
10 min. after the last key operation,
display returns to the initial
parameter set by
b038
. Two option
codes:
00
…
Disable
01
…
Enable
9
00
−
b165
Ex. operator com. loss action
Five option codes:
00
…
Trip
01
…
Trip after deceleration to a stop
02
…
Ignore
03
…
Coasting (FRS)
04
…
Decelerates to a stop
9
02
−
b166
Data Read/Write select
00
…
Read/Write OK
01
…
Protected
U
00
−
b171
Inverter mode selection
Three option codes:
00
…
No function
01
…
Std. IM (Induction Motor)
03
…
PM(Permanent Magnet Motor)
U
00
−
b180
Initialization trigger
(*)
This is to perform initialization by
parameter input with
b084
,
b085
and
b094
. Two option codes:
00
…
Initialization disable
01
…
Perform initialization
U
00
−
b190
Password Settings A
0000(Invalid Password)
0001-FFFF(Password)
U
0000
−
b191
Password authentication A
0000-FFFF
U
0000
−
b192
Password Settings B
0000(Invalid Password)
0001-FFFF(Password)
U
0000
−
b193
Password authentication B
0000-FFFF
U
0000
−