63
“C” Function
Defaults
Func.
Code
Name
Description
Run
Mode
Edit
Initial data
Units
C102
Reset selection
Determines response to Reset
input [RS].
Four option codes:
00
…
Cancel trip state at input signal
ON transition, stops inverter if
in Run Mode
01
…
Cancel trip state at signal OFF
transition, stops inverter if in
Run Mode
02
…
Cancel trip state at input ON
transition, no effect if in
Run Mode
03
…
Clear the memories
only related to trip status
U
00
−
C103
Restart mode after reset
Determines the restart mode after
reset is given, three option codes:
00
…
Start with 0 Hz
01
…
Start with freq. matching
02
…
Start with active freq. matching
U
00
−
C104
UP/DWN clear mode
Freq. set value when UDC signal is
given to the input terminal, two
option codes:
00
…
0 Hz
01
…
Original setting (in the
EEPROM memory at power on)
U
00
−
C105
EO gain adjustment
Set range is 50 to 200%
9
100. %
C106
AM gain adjustment
Set range is 50 to 200%
9
100. %
C109
AM bias adjustment
Set range is 0 to 100%
9
0. %
C111
Overload warning level 2
Sets the overload warning signal
level between 0% and 200% (from
0 to two time the rated current of
the inverter)
9
Rated current
x 1.15
A
C130
Output [11] on delay
U
0.0 sec.
C131
Output [11] off delay
Set range is 0.0 to 100.0 sec.
U
0.0 sec.
C132
Output [12] on delay
U
0.0 sec.
C133
Output [12] off delay
Set range is 0.0 to 100.0 sec.
U
0.0 sec.
C140
Relay output on delay
U
0.0 sec.
C141
Relay output off delay
Set range is 0.0 to 100.0 sec.
U
0.0 sec.
C142
Logic output 1 operand A
U
00
−
C143
Logic output 1 operand B
All the programmable functions
available for logic (discrete) outputs
except LOG1 to LOG3, OPO, no
U
00
−
C144
Logic output 1 operator
Applies a logic function to calculate
[LOG] output state,
Three options:
00
…
[LOG] = A AND B
01
…
[LOG] = A OR B
02
…
[LOG] = A XOR B
U
00
−
C145
Logic output 2 operand A
U
00
−
C146
Logic output 2 operand B
All the programmable functions
available for logic (discrete) outputs
except LOG1 to LOG3, OPO, no
U
00
−