Standard Functions
NOTE
:. Mark “
9
” in b031=10 shows the accessible parameters when b031 is set “10”, high
level access.
“A” Function
Defaults
Func.
Code
Name
Description
Run
Mode
Edit
Initial data
Units
A001
Frequency source
U
02
−
A201
Frequency source,
2
nd
motor
Eight options; select codes:
00
…
POT on ext. operator
01
…
Control terminal
02
…
Function F001 setting
03
…
ModBus network input
04
…
Option
06
…
Pulse train input
07
…
via EzSQ
10
…
Calculate function output
U
02
−
A002
Run command source
U
02
−
A202
Run command source,
2
nd
motor
Five options; select codes:
01
…
Control terminal
02
…
Run key on keypad,
or digital operator
03
…
ModBus network input
04
…
Option
U
02
−
A003
Base frequency
Settable from 30 Hz to
the maximum frequency(
A004
)
U
60.0 Hz
A203
Base frequency,
2
nd
motor
Settable from 30 Hz to
the 2
nd
maximum
frequency(
A204
)
U
60.0 Hz
A004
Maximum frequency
Settable from the base
frequency to 400 Hz
U
60.0 Hz
A204
Maximum frequency,
2
nd
motor
Settable from the 2
nd
base
frequency to 400 Hz
U
60.0 Hz
A005
[AT] selection
Three options; select codes:
00
...Select between [O] and [OI]
at [AT] (ON=OI, OFF=O)
02
...Select between [O] and
external POT at [AT]
(ON=POT, OFF=O)
03
...Select between [OI] and
external POT at [AT]
(ON=POT, OFF=OI)
U
00
−
A011
[O] input active range start
frequency
The output frequency
corresponding to the analog
input range starting point,
range is 0.00 to 400.0
U
0.00 Hz
A012
[O] input active range end
frequency
The
output frequency
corresponding to the analog
input range ending point,
range is 0.0 to 400.0
U
0.00 Hz
A013
[O] input active range start
voltage
The starting point (offset) for the
active analog input range,
range is 0. to 100.
U
0. %
A014
[O] input active range end
voltage
The ending point (offset) for the
active analog input range,
range is 0. to 100.
U
100. %