66
Input Function Summary Table
Option
Code
Terminal
Symbol
Function Name
Description
ON
Clears the UP/DWN frequency memory by forcing it to
equal the set frequency parameter F001. Setting
C101
must be set=
00
to enable this function to work
29
UDC
Remote Control Data
Clearing
OFF UP/DWN frequency memory is not changed
ON
Forces the source of the output frequency setting
A001
and the source of the Run command
A002
to be from
the digital operator
31
OPE Operator
Control
OFF Source of output frequency set by
A001
and source of
Run command set by
A002
is used
ON
Bit encoded speed select, Bit 1, logical 1
32
SF1 Multi-speed
Select,
Bit operation Bit 1
OFF Bit encoded speed select, Bit 1, logical 0
ON
Bit encoded speed select, Bit 2, logical 1
33
SF2 Multi-speed
Select,
Bit operation Bit 2
OFF Bit encoded speed select, Bit 2, logical 0
ON
Bit encoded speed select, Bit 3, logical 1
34
SF3 Multi-speed
Select,
Bit operation Bit 3
OFF Bit encoded speed select, Bit 3, logical 0
ON
Bit encoded speed select, Bit 4, logical 1
35
SF4 Multi-speed
Select,
Bit operation Bit 4
OFF Bit encoded speed select, Bit 4, logical 0
ON
Bit encoded speed select, Bit 5, logical 1
36
SF5 Multi-speed
Select,
Bit operation Bit 5
OFF Bit encoded speed select, Bit 5, logical 0
ON
Bit encoded speed select, Bit 6, logical 1
37
SF6 Multi-speed
Select,
Bit operation Bit 6
OFF Bit encoded speed select, Bit 6, logical 0
ON
Bit encoded speed select, Bit 7, logical 1
38
SF7 Multi-speed
Select,
Bit operation Bit 7
OFF Bit encoded speed select, Bit 7, logical 0
ON
Perform overload restriction
39
OLR Overload
Restriction
Source Changeover
OFF Normal
operation
ON
Setting of
b040
is enabled
40
TL
Torque Limit Selection
OFF Max. torque is limited with 200%
ON
41
TRQ1
Torque limit switch 1
OFF
ON
42
TRQ2
Torque limit switch 2
OFF
Torque limit related parameters of Powering/regen, and
FW/RV modes are selected by the combinations of
these inputs.
ON
Brake wait time (
b124
) is valid
44
BOK Brake
confirmation
OFF Brake wait time (
b124
) is not valid
ON
Set ramp times are ignored. Inverter output
immediately follows the freq. command.
46
LAC LAD
cancellation
OFF Accel. and/or decel. is according to the
set ramp time
ON
Clear the position deviation data
47
PCLR Pulse
counter
clear
OFF Maintain the position deviation data
ON
Adds the
A145
(add frequency) value
to the output frequency
50
ADD
ADD frequency enable
OFF Does not add the
A145
value to the
output frequency
ON
Force inverter to use input terminals
for output frequency and Run command sources
51
F-TM Force
Terminal
Mode
OFF Source of output frequency set by
A001
and source of
Run command set by
A002
is used
ON
Torque control command input is enabled
52
ATR Enable
torque
command input
OFF Torque control command input is disabled
ON Clear
watt-hour
data
53
KHC Clear
watt-hour
data
OFF No
action
ON
General purpose input (1) is made ON under EzSQ
56
MI1
General purpose input
(1)
OFF General purpose input (1) is made OFF under EzSQ
ON
General purpose input (2) is made ON under EzSQ
57
MI2
General purpose input
(2)
OFF General purpose input (2) is made OFF under EzSQ