2
Terminal symbols and Screw size
Inverter Model
Screw Size
Required
Torque (N-m)
Wire range
WJ200-004M M3.5 1.2
AWG12
(3.3mm
2
)
WJ200-007M M4 1.4
AWG10
(5.3mm
2
)
Fuse Sizes
The inverter shall be connected with a UL Listed Cartridge Nonrenewable fuse, rated 600Vac
with the current ratings as shown in the table below or Type E Combination Motor Controller
marking is to indicate that the unit shall be connected with, LS Industrial System Co., Ltd, Type E
Combination Motor Controller MMS Series with the ratings as shown in the table below:
Inverter Model
Fuse (UL-rated, class J, 600V ,
Maximum allowable current)
Type E C.M.C.
WJ200-004M
WJ200-007M
50A, AIC 200kA
MMS-32H,
120 V, 40 A