75
“P” Function
Defaults
Func.
Code
Name
Description
Run
Mode
Edit Initial data Units
p041
Speed / Torque control
switching time
Set range is 0 to 1000 ms
U
0.
ms
P044
Communication watchdog
timer
(for option)
Set range is 0.00 to 99.99s
U
1.00
s
P045
Inverter
action on
communication error
(for option)
00 (tripping),
01 (tripping after decelerating and
stopping the motor),
02 (ignoring errors),
03 (stopping the motor after
free-running),
04 (decelerating and stopping
the motor)
U
00
−
P046
DeviceNet polled I/O:
Output instance number
0-20
U
1
−
P048
Inverter action on
communication idle mode
00 (tripping),
01 (tripping after decelerating and
stopping the motor),
02 (ignoring errors),
03 (stopping the motor after
free-running),
04 (decelerating and stopping the
motor)
U
00
−
P049
Motor poles setting for RPM
0/2/4/6/8/10/12/14/16/18/20/22/24/26
/28/
30/32/34/36/38/40/42/44/46/48
U
0
−
p055
Pulse train input frequency
scale setting
Sets the pulse numbers at max.
frequency, set range is 1.0~32.0 kHz
U
25.0
kHz
p056
Pulse train input frequency
filter time constant setting
Set range is 0.01~2.00 sec.
U
0.10
sec.
p057
Pulse train input bias setting
Set range is –100~100 %
U
0.
%
p058
Limitation of the pulse train
input setting
Set range is 0~100 %
U
100.
%
P060
Multistage position 0
9
0
−
P061
Multistage position 1
9
0
−
P062
Multistage position 2
9
0
−
P063
Multistage position 3
9
0
−
P064
Multistage position 4
9
0
−
P065
Multistage position 5
9
0
−
P066
Multistage position 6
9
0
−
P067
Multistage position 7
P073 to P072
(Displayed higher 4-digits only)
9
0
−
P068
Homing mode selection
00
…Low speed mode
01
…High speed mode
9
00
−
P069
Homing direction
00
…Forward rotation side
01
…Reverse rotation side
9
01
−
P070
Low speed homing freq.
0 to 10Hz
9
5.00 Hz
P071
High speed homing freq.
0 to 400Hz
9
5.00 Hz
P072
Position range (Forward)
0 to +268435455(Higher 4-digits
displayed)
9
+268435
455
−
P073
Position range (Reverse)
–268435455 to 0(Higher 4-digits
displayed)
9
-2684354
55
−