60
“C” Function
Defaults
Func.
Code
Name
Description
Run
Mode
Edit
Initial data
Units
C028
[AM] terminal selection
(Analog voltage output
0...10V)
11 programmable functions:
00
…
Output frequency
01
…
Output current
02
…
Output torque
04
…
Output voltage
05
…
Input power
06
…
Electronic thermal load ratio
07
…
LAD frequency
10
…
Heat sink temperature
11
…
Output torque (with code)
13
…
General output
16
…
Option
U
07
[LAD]
−
C030
Digital current monitor
reference value
Current with digital current monitor
output at 1,440Hz
Range is 20%~200% of rated
current
9
Rated
current
A
C031
Output [11] active state
U
00
−
C032
Output [12] active state
U
00
−
C036
Alarm relay active state
Select logic conversion, two option
codes:
00
…
normally open [NO]
01
…
normally closed [NC]
U
01
−
C038
Output mode of low current
detection
Two option codes:
00
…
During acceleration,
deceleration and constant speed
01
…
During constant speed only
U
01
−
C039
Low current detection level
Set the level of low load detection,
range is 0.0 to 2.0*inverter rated
current
U
INV rated
current
A
C040
Output mode of overload
warning
Two option codes:
00
…
During accel., decel. And
constant speed
01
…
During constant speed only
U
01
−
C041
Overload warning level
Sets the overload warning signal
level between 0% and 200% (from
0 to two time the rated current of
the inverter)
U
Rated current
x 1.15
A
C241
Overload warning level, 2
nd
motor
Sets the overload warning signal
level between 0% and 200% (from
0 to two time the rated current of
the inverter)
U
Rated current
x 1.15
A
C042
Frequency arrival setting
for acceleration
Sets the frequency arrival setting
threshold for the output frequency
during acceleration,
range is 0.0 to 400.0 Hz
U
0.0 Hz
C043
Frequency arrival setting
for deceleration
Sets the frequency arrival setting
threshold for the output frequency
during deceleration,
range is 0.0 to 400.0 Hz
U
0.0 Hz
C044
PID deviation level
Sets the allowable PID loop error
magnitude (absolute value),
SP-PV, range is 0.0 to 100%
U
3.0 %
C045
Frequency arrival setting 2
for acceleration
Set range is 0.0 to 400.0 Hz
U
0.00 Hz
C046
Frequency arrival setting 2
for deceleration
Set range is 0.0 to 400.0 Hz
U
0.00 Hz