10
Using the Front Panel Keypad
Please take a moment to familiarize yourself with the keypad layout shown in the figure
below. The display is used in programming the inverter’s parameters, as well as monitoring
specific parameter values during operation.
Key and Indicator Legend
Items
Contents
(1) POWER LED
Turns ON (Green) while the inverter is powered up.
(2) ALARM LED
Turns ON (Red) when the inverter trips.
(3) Program LED
¾
Turns ON (Green) when the display shows changeable parameter.
¾
Blinks when there is a mismatch in setting.
(4) RUN LED
Turns ON (Green) when the inverter is driving the motor.
(5) Monitor LED [Hz]
Turns ON (Green) when the displayed data is frequency related.
(6) Monitor LED [A]
Turns ON (Green) when the displayed data is current related.
(7) Run command LED
Turns ON (Green) when the RUN command source is set to the operator. (Run key is
effective.)
(8) 7-seg LED
Shows each parameter, monitors etc.
(9) RUN key
Makes inverter run.
(10) STOP/RESET key
¾
Makes inverter stop, according to parameter setup.
¾
Reset the inverter when it is in trip situation
(11) ESC key
¾
Go to the top of next function group, when a function mode is shown
¾
Cancel the setting and return to the function code, when a data is shown
¾
Moves the cursor to a digit left, when it is in digit-to-digit setting mode
¾
Pressing for 1 second leads to display data of
d001
, regardless of current display.
(12) Up key
(13) Down key
¾
Increase or decrease the data.
¾
Pressing the both keys at the same time gives you the digit-to-digit edit.
(14) SET key
¾
Go to the data display mode when a function code is shown
¾
Stores the data and go back to show the function code, when data is shown.
¾
Moves the cursor to a digit right, when it is in digit-to-digit display mode
(15) USB connector
Connect USB connector (mini-B) for using PC communication
(16) RJ45 connector
Connect RJ45 jack for remote operator
1
2
RUN
ESC
STOP/
RESET
SET
8888
RUN
Hz
A
PWR
ALM
PRG
(1) POWER LED
(2) ALARM LED
(8) 7-seg LED
(4) RUN LED
(10) STOP/RESET key
(15) USB connector
(3) Program LED
(16) RJ45 connector
(14) SET key
(13) Down key
(12) Up key
(11) ESC key
(9) RUN key
(7) Run command LED
(5) Monitor LED [Hz]
(6) Monitor LED [A]