55
“b” Function
Defaults
Func.
Code
Name
Description
Run
Mode
Edit
Initial data Units
B054
Initial freq. drop of ctrl. decel.
Setting of initial freq. drop.
Range is 0.0 to 10.0 Hz
U
0.0 Hz
B060
Maximum-limit level of window
comparator (O)
Set range, {Min.-limit level (
b061
) +
hysteresis width (
b062
)x2} to 100 %
(Minimum of 0%)
U
100. %
B061
Minimum-limit level of window
comparator (O)
Set range, 0 to {Max.-limit level
(
b060
) - hysteresis width
(
b062
)x2} % (Maximum of 0%)
9
0. %
B062
Hysteresis width of window
comparator (O)
Set range, 0 to {Max.-limit level
(
b060
) - Min.-limit level (
b061
)}/2 %
(Maximum of 10%)
9
0. %
B063
Maximum-limit level of window
comparator (OI)
Set range, {Min.-limit level (
b064
+
hysteresis width (
b065
)x2} to 100 %
(Minimum of 0%)
9
100. %
B064
Minimum-limit level of window
comparator (OI)
Set range, 0 to {Max.-limit level
(
b063
) - hysteresis width
(
b065
)x2} % (Maximum of 0%)
9
0. %
b065
Hysteresis width of window
comparator (OI)
Set range, 0 to {Max.-limit level
(
b063
) - Min.-limit level (
b064
)}/2 %
(Maximum of 10%)
9
0. %
b070
Operation level at O
disconnection
Set range, 0 to 100%, or “no”
(ignore)
U
no
−
b071
Operation level at OI
disconnection
Set range, 0 to 100%, or “no”
(ignore)
U
no
−
b075
Ambient temperature setting
Set range is,
-10~50
°
C
9
40
°
C
B078
Watt-hour clearance
Two option codes:
00
…
OFF
01
…
ON (press STR then clear)
9
00
−
b079
Watt-hour display gain
Set range is,
1.~1000.
9
1.
B082
Start frequency
Sets the starting frequency for the
inverter output, range is 0.10 to 9.99
Hz
U
0.50 Hz
B083
Carrier frequency
Sets the PWM carrier (internal
switching frequency), range is 2.0 to
15.0 kHz
U
2.0 kHz
B084
Initialization mode (parameters
or trip history)
Select initialized data, five option
codes:
00
…
Initialization disabled
01
…
Clears Trip history
02
…
Initializes all Parameters
03
…
Clears Trip history and
initializes all parameters
04
…
Clears Trip history and
initializes all parameters and
EzSQ program
U
00
−
B085
Country for initialization
Select default parameter values for
country on initialization, two option
codes:
00
…
area A
01
…
area B
U
00
−
B086
Frequency scaling conversion
factor
Specify a constant to scale the
displayed frequency for
D007
monitor, range is 0.01 to 99.99
U
1.00
−