76
“P” Function
Defaults
Func.
Code
Name
Description
Run
Mode
Edit Initial data Units
P075
Positioning mode selection
00
…With limitation
01
…No limitation (shorter route)
P004 is to be set 00 or 01
U
00
−
P077
Encoder disconnection
timeout
0.0 to 10.0 s
9
1.0 sec.
p100
~
P131
EzSQ user parameter
U(00) ~ U(31)
Each set range is 0~65535
9
0.
−
P140
EzCOM number of data
1 to 5
9
5
−
P141
EzCOM destination 1 address
1 to 247
9
1
−
P142
EzCOM destination 1 register
0000 to FFFF
9
0000
−
P143
EzCOM source 1 register
0000 to FFFF
9
0000
−
P144
EzCOM destination 2 address
1 to 247
9
2
−
P145
EzCOM destination 2 register
0000 to FFFF
9
0000
−
P146
EzCOM source 2 register
0000 to FFFF
9
0000
−
P147
EzCOM destination 3 address
1 to 247
9
3
−
P148
EzCOM destination 3 register
0000 to FFFF
9
0000
−
P149
EzCOM source 3 register
0000 to FFFF
9
0000
−
P150
EzCOM destination 4 address
1 to 247
9
4
−
P151
EzCOM destination 4 register
0000 to FFFF
9
0000
−
P152
EzCOM source 4 register
0000 to FFFF
9
0000
−
P153
EzCOM destination 5 address
1 to 247
9
5
−
P154
EzCOM destination 5 register
0000 to FFFF
9
0000
−
P155
EzCOM source 5 register
0000 to FFFF
9
0000
−