Troubleshooting file-level access operations
Problem
Cause
Recovery
The Status lamp on the
main window turns red or
amber. When Event Log is
checked, the error related
to the network link is
shown.
There is a problem with
the external servers (NIS,
LDAP, NFS Export Active
Directory, CIFS).
Recover the external servers to normal
operation.
Link aggregation is not set
properly.
Confirm that the same setting is used
between the NAS module and the client
PC to be connected to the NAS module or
the switch. For more information about
setting link aggregation, see the Hitachi
Virtual Storage Platform Installation and
Reference Guide for your storage system
model.
The host or the client PC
cannot access the file
system
There is a problem with
the external servers (NIS,
LDAP, NFS Export Active
Directory, CIFS).
Recover the external servers to normal
operation.
The settings of the
external servers (NIS,
LDAP, NFS Export Active
Directory, CIFS) are
incorrect.
Correct the external server settings. For
more information about setting the NIS
or LDAP directory service and sharing file
systems, see the Hitachi Virtual Storage
Platform Installation and Reference Guide
for your storage system model.
Troubleshooting the maintenance utility
Maintenance utility port numbers
Use the following table as a reference when changing port numbers for the
maintenance utility.
Port Number
Description
Can the port be closed?
80
Maintenance utility (HTTP)
Yes
Use the maintenance utility.
161
SNMP (udp)
No
443
Maintenance utility (HTTPS)
No
1900
UPnP
Yes
Requires upgrading firmware
before adjusting port access.
10500
MAPP connection
No
31001
RAID Manager
No
338
Troubleshooting the storage system
Service Guide for VSP Gx00 and VSP Fx00 Models
Summary of Contents for Virtual Storage Platform F400
Page 4: ...4 Service Guide for VSP Gx00 and VSP Fx00 Models ...
Page 22: ...22 Preface Service Guide for VSP Gx00 and VSP Fx00 Models ...
Page 106: ...106 Replacing storage system components Service Guide for VSP Gx00 and VSP Fx00 Models ...
Page 140: ...140 Replacing a fan Service Guide for VSP Gx00 and VSP Fx00 Models ...
Page 146: ... CBLM CBLH 146 Replacing a power supply Service Guide for VSP Gx00 and VSP Fx00 Models ...
Page 160: ...160 Replacing a power supply Service Guide for VSP Gx00 and VSP Fx00 Models ...
Page 198: ...6 Click Block 198 Replacing cache memory Service Guide for VSP Gx00 and VSP Fx00 Models ...
Page 250: ...250 Replacing a SAS cable Service Guide for VSP Gx00 and VSP Fx00 Models ...
Page 260: ...260 Replacing cache flash memory Service Guide for VSP Gx00 and VSP Fx00 Models ...
Page 268: ...268 Replacing a LAN blade Service Guide for VSP Gx00 and VSP Fx00 Models ...
Page 278: ...278 Replacing a backup module Service Guide for VSP Gx00 and VSP Fx00 Models ...
Page 284: ...284 Replacing a PCIe module Service Guide for VSP Gx00 and VSP Fx00 Models ...
Page 296: ...296 Replacing a PCIe cable connector Service Guide for VSP Gx00 and VSP Fx00 Models ...
Page 302: ...302 Replacing a PCIe cable Service Guide for VSP Gx00 and VSP Fx00 Models ...
Page 312: ...312 General maintenance Service Guide for VSP Gx00 and VSP Fx00 Models ...
Page 397: ...Warning labels on the storage system 397 Service Guide for VSP Gx00 and VSP Fx00 Models ...
Page 405: ...Warning labels on the storage system 405 Service Guide for VSP Gx00 and VSP Fx00 Models ...
Page 412: ...412 Warning labels on the storage system Service Guide for VSP Gx00 and VSP Fx00 Models ...
Page 417: ...Service Guide for VSP Gx00 and VSP Fx00 Models ...