13.4 Event Specifications
227
10
13
Cha
p
ter 13 Spe
cificatio
ns
-4. Sense function
A SENSE START event occurs and sense starts when the upper or lower value is exceeded while sense
is on. While the sense function is operating, measured values are continuously compared to the range
defined by (the measured value when the event last oc the sense threshold) and (the measured
value when the event last occurred - the sense threshold). If the value falls outside this range, a sense
event is generated, and the sense range is updated. When the upper limit or lower limit exceeded event
ends, a SENSE END event is generated, and sense function operation terminates.
If SENSE and SENSE END overlap, SENSE END will have priority. (SENSE START and SENSE END
are not shown on the display.)
13.4 Event Specifications
-1. Event content
See: "Event items, list notation, and saved items" (p.145)
-2. Event detection
Event detection method
• The detection method relative to measured values for each event target is listed in the measure-
ment specifications.
• External events are detected by detecting signal input to the external event (EVENT IN) terminal.
• Manual events are detected when the
MANU EVENT
key is pressed.
• Enabled measurement item events are detected using OR logic.
• Events cannot be detected using maximum, minimum, or average values.
• The threshold setting error is ±1 dgt. relative to the setting.
-3. Event-synchronized save functionality
Event waveform
Approx. 200 ms aggregation (10 cycle/12 cycle) + instantaneous waveforms for 2 cycles before
and after (20 kS/s) (for 400 Hz measurement, 80 16 cycles before and after)
Transient waveform
Instantaneous waveform for 2 ms before and after the transient overvoltage waveform detection
position (2 MS/s)
High-order harmonic waveform
Instantaneous waveform for 40 ms following the first approx. 200 ms aggregation period in which
the reading is greater than the threshold (200 kS/s)
8000 data points
Fluctuation data
Display of RMS fluctuation data every half cycle equivalent to from 0.5 s before the event to 29.5 s
after event (for 400 Hz, measurement, from 0.125 s before to 7.375 s after) as a detailed trend graph
HIOKI PQ3198A961-03
Summary of Contents for PQ3198
Page 2: ...HIOKI PQ3198A961 03...
Page 6: ...Contents iv HIOKI PQ3198A961 03...
Page 20: ...Usage Notes 14 HIOKI PQ3198A961 03...
Page 44: ...2 3 Display Items and Screen Types 38 HIOKI PQ3198A961 03...
Page 58: ...3 8 Turning the Power On and Off Setting the Default Language 52 HIOKI PQ3198A961 03...
Page 102: ...5 8 Factory Settings 96 HIOKI PQ3198A961 03...
Page 198: ...12 4 Downloading Recorded Data to Computer 192 HIOKI PQ3198A961 03...
Page 264: ...14 4 Disposing of the Instrument 258 HIOKI PQ3198A961 03...
Page 296: ...A32 HIOKI PQ3198A961 03...
Page 299: ...Index Index 3 Index Wiring 73 Z Zero adjustment 53 Zero phase A28 HIOKI PQ3198A961 03...
Page 300: ...Index Index 4 HIOKI PQ3198A961 03...
Page 301: ...HIOKI PQ3198A961 03...
Page 302: ...HIOKI PQ3198A961 03...
Page 303: ...HIOKI PQ3198A961 03...
Page 304: ...www hioki com HIOKI PQ3198A961 03...