13.2 Input Specifications/Output Specifications/Measurement Specifications
204
(16) RMS current (Irms)
Measurement method
AC+DC True RMS type
IEC61000-4-30 compliant: 10 cycles (50 Hz) or 12 cycles (60 Hz) (approx. 200 ms)
80 cycles (400 Hz) (approx. 200 ms)
Includes Zero-display range.
Displayed item
RMS current for each channel and AVG (average) RMS current for multiple channels
(for more information,see "13.8 Calculation Formula" (p.232))
Measurement range
See input specifications.
Measurement accuracy
When the measurement frequency is set to 50 Hz/60 Hz:
±
0.1% rdg.
±
0.1% f.s. + current sensor
accuracy
When the measurement frequency is set to 400 Hz:
±
0.2% rdg.
±
0.6% f.s. + current sensor accu-
racy
Event threshold
0 to current range
Sense
Set to 0 to range rating
Event IN
Start of approx. 200 ms aggregation in which threshold was exceeded
Event OUT
Start of approx. 200 ms aggregation in which reading was less than (threshold - hysteresis)
Multiple-phase system treatment
Separate by channel
Saved waveforms
Event waveforms
(17) Current DC value (Idc)
Measurement method
Average value during approx. 200 ms aggregation synchronized to reference channel (CH4 only)
Includes Zero-display range.
Displayed item
Current DC value
Measurement range
Varies with current sensor used.
Measurement accuracy
±
0.5% rdg.
±
0.5% f.s. + current sensor specifications accuracy
Not specified when using AC dedicated current sensor.
Event threshold
0 to (±400% of the current range)
The difference between the positive and negative waveform peak values in the 200 ms aggrega-
tion is compared to the threshold to generate DC fluctuation events.
Event IN
Start of the 200 ms aggregation in which the threshold was exceeded
Event OUT
Start of the first 200 ms aggregation after the IN state in which the threshold was not exceed
Multiple-phase system treatment
None
Saved waveforms
Event waveforms
HIOKI PQ3198A961-03
Summary of Contents for PQ3198
Page 2: ...HIOKI PQ3198A961 03...
Page 6: ...Contents iv HIOKI PQ3198A961 03...
Page 20: ...Usage Notes 14 HIOKI PQ3198A961 03...
Page 44: ...2 3 Display Items and Screen Types 38 HIOKI PQ3198A961 03...
Page 58: ...3 8 Turning the Power On and Off Setting the Default Language 52 HIOKI PQ3198A961 03...
Page 102: ...5 8 Factory Settings 96 HIOKI PQ3198A961 03...
Page 198: ...12 4 Downloading Recorded Data to Computer 192 HIOKI PQ3198A961 03...
Page 264: ...14 4 Disposing of the Instrument 258 HIOKI PQ3198A961 03...
Page 296: ...A32 HIOKI PQ3198A961 03...
Page 299: ...Index Index 3 Index Wiring 73 Z Zero adjustment 53 Zero phase A28 HIOKI PQ3198A961 03...
Page 300: ...Index Index 4 HIOKI PQ3198A961 03...
Page 301: ...HIOKI PQ3198A961 03...
Page 302: ...HIOKI PQ3198A961 03...
Page 303: ...HIOKI PQ3198A961 03...
Page 304: ...www hioki com HIOKI PQ3198A961 03...