12.1 LR8410-20 Wireless Logging Station Specifications
282
Split Save
Selectable Off, On or Periodic
• On:
Saves data split into separate files from measurement start,
at the set interval.
• Periodic: Saves data split into separate files from a set reference time
(within 24 hours), at the set interval.
Deleting
Selectable Off or On
• On: Deletes the oldest file to save the newest file when removable
storage becomes
Remove external
media
During real-time saving, press a button, confirm the displayed message,
and remove the storage media.
When the removable media is re-inserted, data retained in internal mem-
ory is saved continuously to a separate file.
Data protection
If a power outage occurs or the battery runs out during real-time saving,
power is cut off after the file is closed (protection becomes possible
approximately 10 min. or more after the instrument is turned on).
Manual saving
Press SAVE to save.
Select SAVE operation from selection or immediate saving.
During immediate saving, the save type, format, range, and filename are
set in advance. The filename can be entered when saving.
Save types
Setting criteria, waveform data (binary format), waveform data (CSV for-
mat),numerical calculation results, screen captures (compressed bitmap
format), reservation settings
Reloading data
Up to 8 M data values can be saved in binary format to a specified loca-
tion. (one analog channel recording time, or 8 M / n values for n channels)
(where n = number of analog and logic ch number of pulse (inte-
gration, RPM) ch number of waveform calculation channels × 4
+ alarm data, where alarm data is 36 when an alarm is in use or 0 when
not in use)
Save
Calculations
Numerical calculations
No. of calculations
Six calculations are available at the same time
Calculations
Average value, peak value, maximum value, Time to maximum value,
minimum value, Time to minimum value
Calculation time
span
(After measuring)
Applies calculations to all data in internal buffer memory, or to the time-
span specified by A/B cursors.
Calculation time
span
(While measuring)
Applies calculations to all data in internal buffer memory
.
Interval calculation:
Values are calculated for each specified timeframe, and the latest calcu-
lated value is displayed.
Select from time periods (segment times) of 1 min., 2 min., 5 min., 10
min., 15 min., 20 min., 30 min., 1 h., 2 h., 3 h., 4 h., 6 h., 8 h., 12 h., and
1 day.
Summary of Contents for LR8410-20
Page 1: ......
Page 2: ......
Page 12: ...Contents x...
Page 32: ...Operating Precautions 20...
Page 78: ...2 7 Compensating for Input Circuit Offset Zero Adjustment 66...
Page 122: ...3 10 Viewing and Editing with the All Channel Settings List 110...
Page 138: ...4 3 Marking Waveforms and Searching Marks Search Function 126...
Page 222: ...9 4 Synchronous Measurements with Multiple instruments 210...
Page 316: ...13 3 Disposing of the instrument 304...
Page 360: ...Index Index 4...
Page 361: ......
Page 362: ......
Page 363: ......
Page 364: ......