LED Descriptions
129/299
PC Cards cifX Compact PCI, Mini PCI, Mini PCIe, PCI-104 | Installation, Operation and Hardware Description
DOC120205UM53EN | Revision 53 | English | 2019-03 | Released | Public
© Hilscher, 2008-2019
8.13 PROFINET IO-Controller V2
For the PROFINET IO-Controller protocol, the communication LEDs
SF
(system failure) and
BF
(bus failure) as well as the Ethernet LEDs
LINK
and
RX/TX
can assume the states described below. This description is
valid from stack version V2.6.
LED
Color
State
Meaning
Duo LED red/green
(off)
Off
No error
(red)
Flashing
(1 Hz, 3 s)
DCP signal service
is initiated via the bus.
(red)
Flashing
(2 Hz)
System error:
Invalid configuration, Watchdog error or internal error
SF
(System
Failure)
General
name:
COM 0
(red)
On
(
together
with SF „red
ON
)
No valid Master license
Duo LED red/green
(off)
Off
No error
(red)
Flashing
(2 Hz)
Configuration fault:
Not all configured IO-Devices are connected.
(red)
On
(
together
with SF „red
ON")
No valid Master license
BF
(Bus
Failure)
General
name:
COM 1
(red)
On
(
together
with SF „red
OFF")
No Connection:
No Link.
LED green
(green)
On
The device is linked to the Ethernet.
LINK
Ch0 & Ch1
(off)
Off
The device has no link to the Ethernet.
LED yellow
(gelb)
Flickering
(load de-
pendant)
The device sends/receives Ethernet frames.
RX/TX
Ch0 & Ch1
(off)
Off
The device does not send/receive Ethernet frames.
Table 68: LED states for the PROFINET IO-Controller protocol
LED state
Definition
Flashing
(1 Hz, 3 s)
The indicator turns on and off for 3 seconds with a frequency of 1 Hz: “on” for 500 ms, followed
by “off” for 500 ms.
Flashing (2 Hz)
The indicator turns on and off with a frequency of 2 Hz:
“on” for 250 ms, followed by “off” for 250 ms.
Flickering
(load
dependant)
The indicator turns on and off with a frequency of approximately 10 Hz to indicate high Ethernet
activity: on for approximately 50 ms, followed by off for 50 ms. The indicator turns on and off in
irregular intervals to indicate low Ethernet activity.
Table 69: LED state definitions for the PROFINET IO-Controller protocol