Technical Data
250/299
PC Cards cifX Compact PCI, Mini PCI, Mini PCIe, PCI-104 | Installation, Operation and Hardware Description
DOC120205UM53EN | Revision 53 | English | 2019-03 | Released | Public
© Hilscher, 2008-2019
10.4.17 PROFIBUS DP Master
Parameter
Description
Maximum number of PROFIBUS DP slaves
125 (DPV0/DPV1)
Maximum number of total cyclic input data
5712 bytes
Maximum number of total cyclic output data
5760 bytes
Maximum number of cyclic input data
244 bytes per slave
Maximum number of cyclic output data
244 bytes per slave
Configuration data
Max. 244 bytes per slave
Parameterization data per slave
7 bytes standard parameter per slave
Max. 237 bytes application specific parameters per slave
Acyclic communication
DPV1 class 1 read, write
DPV1 class 1 alarm
DPV1 class 2 initiate, read, write, data transport, abort
Maximum number of acyclic read/write
240 bytes per slave and telegram
Functions
Configuration in Run (CiR), requires host application program
support
Timestamp (Master functionality)
Redundancy Supported,
requires
host application program support
Baud rate
9,6 kBits/s,
19,2 kBits/s,
31,25 kBits/s,
45,45 kBits/s
93,75 kBits/s,
187,5 kBits/s,
500 kBits/s,
1, 5 MBits/s,
3 MBits/s,
6 MBits/s,
12 MBit/s
Auto baud rate detection is not supported
Data transport layer
PROFIBUS FDL
Limitations
DPV2 isochronous mode and slave slave communication are not
supported.
The redundancy function can not be used, if the master is
configured by the host application program by packets.
Reference to firmware/stack version
V2.8
Table 185: Technical Data PROFIBUS DP Master Protocol