9.1.3
Ethernet Connection Data
RJ45
2 x 2 Twisted-Pair copper cable, CAT5 (100 MBit/s)
Medium
M12
2 x cable, CAT5 (100 MBit/s)
Length of cable
max. 100 m
Transmission
rate
10 MBit/s/100 MBit/s
Table 108: Ethernet Connection Data
9.1.4
Use of Hubs and Switches
For the corresponding communication systems, the use of hubs and/or
switches is either forbidden or allowed. The following table shows the
acceptable use of hubs and switches by each communication system:
Communication System
Hub
Switch
EtherCAT
forbidden
only allowed between EtherCAT Master and first EtherCAT Slave
(100 MBit/s, Full Duplex)
EtherNet/IP
allowed
allowed
(10 MBit/s/100 MBit/s, Full or Half Duplex, Auto-Negotiation)
Open Modbus/TCP
allowed
allowed
(10 MBit/s/100 MBit/s, Full or Half Duplex, Auto-Negotiation)
POWELINK
allowed forbidden
PROFINET IO
forbidden
Only allowed if the switch supports ‚Priority Tagging’ and LLDP
(100 MBit/s, Full Duplex)
Sercos
forbidden forbidden
VARAN*
forbidden forbidden
Table 109: Use of Hubs and Switches