Technical Data
185/299
PC Cards cifX Compact PCI, Mini PCI, Mini PCIe, PCI-104 | Installation, Operation and Hardware Description
DOC120205UM53EN | Revision 53 | English | 2019-03 | Released | Public
© Hilscher, 2008-2019
CIFX 90-CC\F
Parameter
Value
Transmission Rate
33 MHz
Data Access
DPM or DMA (Direct Memory Access)
Width for the data access to the
Dual-Port Memory (DPM)
32-Bit
CC-Link
Communication
Supported communication
standard/ protocol (determined by
the loaded firmware)
CC-Link Slave
Transmission rate
156 kBit/s, 625 kBit/s, 2500 kBit/s, 5 MBit/s, 10 MBit/s
Interface Type
RS-485, refer to section
CC-Link detached Network
Interface
page 232.
Important!
Operating the PC card CIFX 90-CC\F requires proper
connection of the CC-Link detached network interface (AIFX-CC)
to the basic card!
CC-Link Interface
Connector AIFX-CC
Connector Fieldbus X3
(JST 10FMN-SMT-A-TF(LF)(SN), Pitch 1,0 mm)
SYS
System Status LED
Display LED
Display
For LEDs at AIFX-CC, refer to section
Supply Voltage
+3.3 V dc ±5 %, refer to section
Current consumption at 3.3 V
650 mA (maximum)
Power supply
Connector
Via Mini PCI Bus
Operating temperature range*
0 °C ... +60 °C
*Air flow during measurment
0,5 m/s
Storage temperature range
-40 °C ... +85 °C
Environmental
Conditions
Humidity
10 … 95% relative humidity, no condensation permitted
Dimensions (L x W x H)
60 x 45 x 11 mm
Mounting/Installation
Mini PCI Socket (3.3 V), Type III System Connector,
refer to section
Slot for the PC Cards cifX Compact PCI,
Device
RoHS Yes
CE Sign
Yes
Emission
EN 55011:2009 + A1:2010, CISPR 11:2009, Class A
(Radio disturbance characteristics - Limits and methods of
measurement)
CE Sign
Immunity
EN 61000-4-2:2009 (Electrostatic discharge test)
EN 61000-4-3:2006 + A1:2008 + A2:2010 (Radiated,
radio-frequency, electromagnetic field test)
EN 61000-4-4:2004 + A1:2010 (Burst Electrical fast
transients/burst test)
EN 61000-4-5:2006 (Surge test)
EN 61000-4-6:2009 (to conducted disturbances, induced
by radio- frequency fields)
EN 61000-4-8:2010 (power frequency magnetic field test)
EN 61000-6-2:2005 + B1:2011 (for industrial
environments)
Configuration Configuration
Software SYCON.net or netX Configuration Tool
Table 139: Technical Data CIFX 90-CC\F