LED Descriptions
128/299
PC Cards cifX Compact PCI, Mini PCI, Mini PCIe, PCI-104 | Installation, Operation and Hardware Description
DOC120205UM53EN | Revision 53 | English | 2019-03 | Released | Public
© Hilscher, 2008-2019
8.12 POWERLINK Controlled Node/Slave V2, V3
For the POWERLINK Controlled Node protocol, the communication LEDs
BS
(Bus Status) and
BE
(Bus Error) as well as the Ethernet LED
L/A
can
assume the states described below. This description is valid from stack
version V2.1 respectively from stack version V3.0.
LED
Color
State
Meaning
Duo LED red/green
(green)
On
Slave is in
‘Operational’
state
(green)
Triple Flash
Slave is in
‚ReadyToOperate’
state
(green)
Double flash
Slave is in
‚Pre-Operational 2’
state
(green)
Single flash
Slave is in
‚Pre-Operational 1’
state
(green)
Flickering
(10 Hz)
Slave is in
‚Basic Ethernet’
state
(green)
Blinking
(2,5 Hz)
Slave is in
‚Stopped’
state
BS
(Bus Status)
General
name:
COM 0
(off)
Off Slave
initializing
Duo LED red/green
(off)
Off
Slave has no error
BE
(Bus Error)
General
name:
COM 1
(red)
On
Slave has detected an error
LED green
(green)
On
Link:
The device is linked to the Ethernet, but does not
send/receive Ethernet frames.
(green)
Flickering (load
dependant)
Activity:
The device is linked to the Ethernet and sends/receives
Ethernet frames.
L/A
Ch0 & Ch1
(off)
Off
The device has no link to the Ethernet.
LED yellow
Ch0 & Ch1
(off)
Off
This LED is not used.
Table 66: LED states for the POWERLINK Controlled Node protocol
LED state
Definition
Triple Flash
The indicator shows a sequence of three short flashes (each 200 ms), separated by a short off
phase (200 ms). The sequence is finished by a long off phase (1,000 ms).
Double flash
The indicator shows a sequence of two short flashes (each 200 ms), separated by a short off
phase (200 ms). The sequence is finished by a long off phase (1,000 ms).
Single flash
The indicator shows one short flash (200 ms) followed by a long “off“ phase (1,000 ms).
Flickering
(10 Hz)
The indicator turns on and off with a frequency of 10 Hz: “on” for 50 ms, followed by off for 50 ms.
The red LED and the green LED are switched on alternately.
Blinking
(2,5 Hz)
The indicator turns on and off phase with a frequency of 2.5 Hz:
on for 200 ms, followed by off for 200 ms. The red LED and the green LED are switched on
alternately.
Flickering (load
dependant)
The indicator turns on and off with a frequency of approximately 10 Hz to indicate high Ethernet
activity: on for approximately 50 ms, followed by off for 50 ms. The indicator turns on and off in
irregular intervals to indicate low Ethernet activity.