1.5 System Device Memory for Communication Confirmation
1-63
1.5.2 $s518 (Ethernet Status Confirmation)
Stores the current status of the Ethernet.
Error details
Address
Contents
Stored Value
$s518
Ethernet status (for built-in LAN port)
[0]: Normal
[Other than 0]: Error
* For details on errors, refer to the next section.
No.
Built-in
LAN
Contents
Solution
201
Send error
Check that the setting on the target station is consistent with the network
table setting.
203
TCP socket creation error
The TCP socket cannot be created. Turn the power off and back on again,
or check the communication line status, e.g., if the port number is
duplicated.
204
TCP connection over
The number of connections reaches the maximum (256), and no more
connection is possible.
Check the communication lines.
205
TCP connection error
Connection cannot be established.
Check the communication lines, or turn the power off and back on again.
207
TCP send error
TCP communication has failed.
Check the communication lines.
208
TCP connection interruption
notification from the connected
device
Check the connected device and communication lines.
261
Send processing full error
Sending process is disabled. Check the communication lines.
350
Send buffer full
The line is busy. Consult the network administrator of your company.
The communication unit is of an old version or is faulty.
801
Link down error
Check the HUB or the link confirmation LED on the communication unit. If
the LED is not on, check cable connection and the port setting on the
network table.
1202
MAC address error
The MAC address is not registered. Repair is necessary.
2001
Undefined error
Turn the power off and back on again.
If the problem persists, the unit may be faulty. Contact your local
distributor.
Summary of Contents for Monitouch V9 Series
Page 76: ...1 64 1 Overview Please use this page freely...
Page 77: ...2 1 PLC Connection 2 ALLEN BRADLEY...
Page 119: ...2 42 2 ALLEN BRADLEY Please use this page freely...
Page 120: ...3 1 PLC Connection 3 Automationdirect...
Page 131: ...4 1 PLC Connection 4 2 Temperature Controller Servo Inverter Connection 4 Azbil...
Page 164: ...5 1 PLC Connection 5 Baumuller...
Page 169: ...6 1 PLC Connection 6 BECKHOFF...
Page 174: ...7 1 Temperature Controller Servo Inverter Connection 7 CHINO...
Page 193: ...8 1 PLC Connection 8 CIMON...
Page 206: ...9 1 PLC Connection 9 DELTA...
Page 211: ...10 1 Temperature Controller Servo Inverter Connection 10 DELTA TAU DATA SYSTEMS...
Page 222: ...11 EATON Cutler Hammer 11 1 PLC Connection...
Page 227: ...12 1 PLC Connection 12 EMERSON...
Page 232: ...13 FANUC 13 1 PLC Connection...
Page 238: ...13 6 13 FANUC Please use this page freely...
Page 239: ...14 Fatek Automation 14 1 PLC Connection...
Page 245: ...14 6 14 Fatek Automation Please use this page freely...
Page 246: ...15 1 PLC Connection 15 FUFENG...
Page 252: ...15 6 15 FUFENG Please use this page freely...
Page 253: ...16 Fuji Electric 16 1 PLC Connection 16 2 Temperature Controller Servo Inverter Connection...
Page 357: ...16 104 16 Fuji Electric Please use this page freely...
Page 358: ...17 1 Temperature Controller Servo Inverter 17 Gammaflux...
Page 364: ...17 6 17 Gammaflux Please use this page freely...
Page 365: ...18 GE Fanuc 18 1 PLC Connection...
Page 380: ...19 1 PLC Connection 19 Hitachi...
Page 394: ...19 14 19 Hitachi Please use this page freely...
Page 423: ...20 28 20 Hitachi Industrial Equipment Systems Please use this page freely...