3-2
3. Automationdirect
3.1.1 Direct LOGIC (K-Sequence)
Communication Setting
Editor
Communication setting
(Underlined setting: default)
D4-450
PORT0
No particular setting is necessary on the PLC. The PLC always performs communication functions using the following
parameters. Set the following parameters under [Communication Setting] of the editor.
PORT1
Set parameters into the special register “R772, 773”, then set “AA5A” (HEX) into the setting complete register “R767”. When
the set value at R767 is changed to “AAAA” (HEX), it is regarded as normal; if it is changed to “AAEA” (HEX), it is regarded as
erroneous.
Parameter setting register
(Underlined setting: default)
Item
Setting
Remarks
Connection Mode
1 : 1 / Multi-link2 / Multi-link2 (Ethernet)
Signal Level
RS-232C / RS-422/485
Baud Rate
4800 / 9600 / 19200 / 38400 bps
Data Length
8
bits
Stop Bit
1 / 2 bits
Parity
None / Odd / Even
Target Port No.
0 to 31
Item
Setting
Baud Rate
9600 bps
Parity
Odd
Data Length
8
Stop Bit
1
Data Type
HEX
Register
Setting
Setting Example
R772
00E0H
K-Sequence
R773
8701H
38400 bps
Odd parity
Stop bit 1
Station number 01
0
0
E
0
Communication protocol
80: K-Sequence
E0: Automatic recognition (Modbus, CCM, K-Sequence)
Communication timeout
0: 800 ms
Response delay time
0: 0 ms
8
7
0
1
Station number
01 to 1F (HEX)
Baud rate
4: 4800 bps
5: 9600 bps
6: 19200 bps
7: 38400 bps
Parity stop bit
0: Without parity, stop bit 1
2: Without parity, stop bit 2
8: Odd parity, stop bit 1
A: Odd parity, stop bit 2
C: Even parity, stop bit 1
E: Even parity, stop bit 2
Summary of Contents for Monitouch V9 Series
Page 76: ...1 64 1 Overview Please use this page freely...
Page 77: ...2 1 PLC Connection 2 ALLEN BRADLEY...
Page 119: ...2 42 2 ALLEN BRADLEY Please use this page freely...
Page 120: ...3 1 PLC Connection 3 Automationdirect...
Page 131: ...4 1 PLC Connection 4 2 Temperature Controller Servo Inverter Connection 4 Azbil...
Page 164: ...5 1 PLC Connection 5 Baumuller...
Page 169: ...6 1 PLC Connection 6 BECKHOFF...
Page 174: ...7 1 Temperature Controller Servo Inverter Connection 7 CHINO...
Page 193: ...8 1 PLC Connection 8 CIMON...
Page 206: ...9 1 PLC Connection 9 DELTA...
Page 211: ...10 1 Temperature Controller Servo Inverter Connection 10 DELTA TAU DATA SYSTEMS...
Page 222: ...11 EATON Cutler Hammer 11 1 PLC Connection...
Page 227: ...12 1 PLC Connection 12 EMERSON...
Page 232: ...13 FANUC 13 1 PLC Connection...
Page 238: ...13 6 13 FANUC Please use this page freely...
Page 239: ...14 Fatek Automation 14 1 PLC Connection...
Page 245: ...14 6 14 Fatek Automation Please use this page freely...
Page 246: ...15 1 PLC Connection 15 FUFENG...
Page 252: ...15 6 15 FUFENG Please use this page freely...
Page 253: ...16 Fuji Electric 16 1 PLC Connection 16 2 Temperature Controller Servo Inverter Connection...
Page 357: ...16 104 16 Fuji Electric Please use this page freely...
Page 358: ...17 1 Temperature Controller Servo Inverter 17 Gammaflux...
Page 364: ...17 6 17 Gammaflux Please use this page freely...
Page 365: ...18 GE Fanuc 18 1 PLC Connection...
Page 380: ...19 1 PLC Connection 19 Hitachi...
Page 394: ...19 14 19 Hitachi Please use this page freely...
Page 423: ...20 28 20 Hitachi Industrial Equipment Systems Please use this page freely...