16.2 Temperature Controller/Servo/Inverter Connection
16-33
Macro
To rewrite the station number table on the V series screen, use macro commands [FROM_WR] and [RESTART].
FROM_WR
FROM_WR F0 F1
Function: Writing to FROM
As many words as specified for F1 from the device memory address set for F0 is written in the FP-ROM.
Available device memory
Data range
Notes
- The maximum possible number of write operations to the FP-ROM is 100,000 times. This is not related to the number
of words that are written.
- Do not include the FROM_WR command in a cycle macro or an event timer macro.
- Writing to FP-ROM takes a longer time.
- When the station number table has been rewritten using the [FROM_WR] command, be sure to execute the [RESTART]
command.
- When the station number table is used, it is not possible to set [ Use Internal Flash ROM as Back-up Area] on the
[General Settings] tab window that is displayed by selecting [System Setting]
[Unit Setting]
[General Settings]. Be
sure to leave this box unchecked.
RESTART
SYS (RESTART) F0
Function: Reconnection
This macro command reconnects the controller when the time specified for F1 has elapsed.
Available device memory
Data range
Internal Device
Memory
PLC n Device Memory
Memory Card
Constant
F0
F1
: Setting enabled (indirect designation disabled)
: Setting enabled (indirect designation enabled)
Setting
Remarks
F0
Top device memory
address of the source
32 words from the top address of the specified device memory are used.
Set port numbers from 0 to 31 for each address. For the station number
table not used, set [
1].
F1
Number of transmission
words: 32
If any other value than “32” is set, the write error ($s728 = 1) occurs.
When the station number table has been rewritten using the [FROM_WR] command, be sure to execute this command.
Internal Device
Memory
PLC n Device Memory
Memory Card
Constant
F1
: Setting enabled (indirect designation disabled)
: Setting enabled (indirect designation enabled)
Setting
F0
RESTART
F1
Time: 0 to 60 s
Summary of Contents for Monitouch V9 Series
Page 76: ...1 64 1 Overview Please use this page freely...
Page 77: ...2 1 PLC Connection 2 ALLEN BRADLEY...
Page 119: ...2 42 2 ALLEN BRADLEY Please use this page freely...
Page 120: ...3 1 PLC Connection 3 Automationdirect...
Page 131: ...4 1 PLC Connection 4 2 Temperature Controller Servo Inverter Connection 4 Azbil...
Page 164: ...5 1 PLC Connection 5 Baumuller...
Page 169: ...6 1 PLC Connection 6 BECKHOFF...
Page 174: ...7 1 Temperature Controller Servo Inverter Connection 7 CHINO...
Page 193: ...8 1 PLC Connection 8 CIMON...
Page 206: ...9 1 PLC Connection 9 DELTA...
Page 211: ...10 1 Temperature Controller Servo Inverter Connection 10 DELTA TAU DATA SYSTEMS...
Page 222: ...11 EATON Cutler Hammer 11 1 PLC Connection...
Page 227: ...12 1 PLC Connection 12 EMERSON...
Page 232: ...13 FANUC 13 1 PLC Connection...
Page 238: ...13 6 13 FANUC Please use this page freely...
Page 239: ...14 Fatek Automation 14 1 PLC Connection...
Page 245: ...14 6 14 Fatek Automation Please use this page freely...
Page 246: ...15 1 PLC Connection 15 FUFENG...
Page 252: ...15 6 15 FUFENG Please use this page freely...
Page 253: ...16 Fuji Electric 16 1 PLC Connection 16 2 Temperature Controller Servo Inverter Connection...
Page 357: ...16 104 16 Fuji Electric Please use this page freely...
Page 358: ...17 1 Temperature Controller Servo Inverter 17 Gammaflux...
Page 364: ...17 6 17 Gammaflux Please use this page freely...
Page 365: ...18 GE Fanuc 18 1 PLC Connection...
Page 380: ...19 1 PLC Connection 19 Hitachi...
Page 394: ...19 14 19 Hitachi Please use this page freely...
Page 423: ...20 28 20 Hitachi Industrial Equipment Systems Please use this page freely...