16-54
16. Fuji Electric
16.2.15FRENIC-Eco (MODBUS RTU)
Communication Setting
Editor
Communication setting
(Underlined setting: default)
Inverter
Set communication parameters.
Be sure to match the settings to those made under [Communication Setting] of the editor.
(Underlined setting: default)
Item
Setting
Remarks
Connection Mode
1
:
1 / 1
:
n / Multi-link2 / Multi-link2 (Ethernet) /
1
:
n Multi-link2 (Ethernet)
Signal Level
RS-422/485
Baud Rate
4800 / 9600 / 19200 / 38400 bps
Data Length
8 bits
Do not change the default setting because the setting on
the inverter cannot be changed.
Stop Bit
1 / 2 bits
When no parity setting is made, “2 bits” is set for stop bit.
When a parity setting is made, “1 bit” is set for stop bit.
Parity
None / Odd / Even
Target Port No.
1 to 31
Function
Code
Item
Setting
Example
y01
RS-485
setting
(touch
panel)
Station address
1 to 31
1
y04
Baud rate
1: 4800 bps
2: 9600 bps
3: 19200 bps
4: 38400 bps
3
y06
Parity bit
0: None
1: Even
2: Odd
0
y07
Stop bit
For Modbus RTU communication, the stop bit setting is automatically
made according to the parity bit setting.
When no parity setting is made, “2 bits” is set for stop bit.
When a parity setting (even or odd) is made, “1 bit” is set for stop bit.
-
y10
Communication
protocol
*1
0: Modbus RTU
1: SX (loader) protocol
2: FGI-bus
0
y11
RS-485
setting 2
(optional
board)
Station address
1 to 31
1
y14
Baud rate
1: 4800 bps
2: 9600 bps
3: 19200 bps
4: 38400 bps
3
y16
Parity bit
0: None
1: Even
2: Odd
0
y17
Stop bit
For Modbus RTU communication, the stop bit setting is automatically
made according to the parity bit setting.
When no parity setting is made, “2 bits” is set for stop bit.
When a parity setting (even or odd) is made, “1 bit” is set for stop bit.
-
y20
Communication
protocol
*1
0: Modbus RTU
2: FGI-bus
0
y98
Bus function
0
y99
Support link function
0
Frequency
Operation Command
0
Function code H30
Function code H30
1
Commanded from the fieldbus
Function code H30
2
Function code H30
Commanded from the fieldbus
3
Commanded from the fieldbus
Commanded from the fieldbus
Frequency
Operation Command
0
Function code H30, y98
Function code H30, y98
1
Commanded from RS-485
Function code H30, y98
2
Function code H30, y98
Commanded from RS-485
3
Commanded from RS-485
Commanded from RS-485
Summary of Contents for Monitouch V9 Series
Page 76: ...1 64 1 Overview Please use this page freely...
Page 77: ...2 1 PLC Connection 2 ALLEN BRADLEY...
Page 119: ...2 42 2 ALLEN BRADLEY Please use this page freely...
Page 120: ...3 1 PLC Connection 3 Automationdirect...
Page 131: ...4 1 PLC Connection 4 2 Temperature Controller Servo Inverter Connection 4 Azbil...
Page 164: ...5 1 PLC Connection 5 Baumuller...
Page 169: ...6 1 PLC Connection 6 BECKHOFF...
Page 174: ...7 1 Temperature Controller Servo Inverter Connection 7 CHINO...
Page 193: ...8 1 PLC Connection 8 CIMON...
Page 206: ...9 1 PLC Connection 9 DELTA...
Page 211: ...10 1 Temperature Controller Servo Inverter Connection 10 DELTA TAU DATA SYSTEMS...
Page 222: ...11 EATON Cutler Hammer 11 1 PLC Connection...
Page 227: ...12 1 PLC Connection 12 EMERSON...
Page 232: ...13 FANUC 13 1 PLC Connection...
Page 238: ...13 6 13 FANUC Please use this page freely...
Page 239: ...14 Fatek Automation 14 1 PLC Connection...
Page 245: ...14 6 14 Fatek Automation Please use this page freely...
Page 246: ...15 1 PLC Connection 15 FUFENG...
Page 252: ...15 6 15 FUFENG Please use this page freely...
Page 253: ...16 Fuji Electric 16 1 PLC Connection 16 2 Temperature Controller Servo Inverter Connection...
Page 357: ...16 104 16 Fuji Electric Please use this page freely...
Page 358: ...17 1 Temperature Controller Servo Inverter 17 Gammaflux...
Page 364: ...17 6 17 Gammaflux Please use this page freely...
Page 365: ...18 GE Fanuc 18 1 PLC Connection...
Page 380: ...19 1 PLC Connection 19 Hitachi...
Page 394: ...19 14 19 Hitachi Please use this page freely...
Page 423: ...20 28 20 Hitachi Industrial Equipment Systems Please use this page freely...