1-60
1.
Overview
$Pn: 100 to 355
The results of communication with each station are stored here. The status codes are shown below.
Errors other than the above are stored as shown below.
Solution
1) Check if the communication settings of the V9 series and the connected device are matched.
2) Check the cable connection.
3) Data may be disrupted because of noise. Fix noise.
If you still cannot solve the error even after following the solutions above, contact your local distributor.
Code (HEX)
Contents
0000H
Normal
FFFFH
Time-out
8001H
Check code error
8002H
Data error
800BH
Receives the error code from the connected device
Error
Details
Solution
Time-out
Although a request to send is given, no answer is
returned within the specified time.
Implement solutions 1, 2, and 3.
Check code
The check code of the response is incorrect.
Implement solutions 1 and 3.
Data error
The code of the received data is invalid.
Implement solutions 1, 2, and 3.
Error code received
An error occurred on the connected device.
Refer to the instruction manual for the PLC.
Buffer full
The V9 buffer is full.
Contact your local distributor.
Parity
An error occurred in parity check.
Implement solutions 2 and 3.
Overrun
After receiving one character, the next character was
received before internal processing was completed.
Implement solutions 1 and 3.
Framing
Although the stop bit must be “1”, it was detected as
“0”.
Implement solutions 1, 2, and 3.
Break detection
The connected device’s SD is remaining at the low
level.
Examine the connection with the connected device’s
SD and RD.
Buffer-full error
Parity error
Overrun error
Framing error
Break detection
15 14 13 12 11 10
9
8
7
6
5
4
3
2
1
0
0
0
0
0
0
0
0
0
0
0
MSB
LSB
Error
0: Bits 0 to 14 are all “0”.
1: Any bit from 0 to 14 is other than “0”.
Summary of Contents for Monitouch V9 Series
Page 76: ...1 64 1 Overview Please use this page freely...
Page 77: ...2 1 PLC Connection 2 ALLEN BRADLEY...
Page 119: ...2 42 2 ALLEN BRADLEY Please use this page freely...
Page 120: ...3 1 PLC Connection 3 Automationdirect...
Page 131: ...4 1 PLC Connection 4 2 Temperature Controller Servo Inverter Connection 4 Azbil...
Page 164: ...5 1 PLC Connection 5 Baumuller...
Page 169: ...6 1 PLC Connection 6 BECKHOFF...
Page 174: ...7 1 Temperature Controller Servo Inverter Connection 7 CHINO...
Page 193: ...8 1 PLC Connection 8 CIMON...
Page 206: ...9 1 PLC Connection 9 DELTA...
Page 211: ...10 1 Temperature Controller Servo Inverter Connection 10 DELTA TAU DATA SYSTEMS...
Page 222: ...11 EATON Cutler Hammer 11 1 PLC Connection...
Page 227: ...12 1 PLC Connection 12 EMERSON...
Page 232: ...13 FANUC 13 1 PLC Connection...
Page 238: ...13 6 13 FANUC Please use this page freely...
Page 239: ...14 Fatek Automation 14 1 PLC Connection...
Page 245: ...14 6 14 Fatek Automation Please use this page freely...
Page 246: ...15 1 PLC Connection 15 FUFENG...
Page 252: ...15 6 15 FUFENG Please use this page freely...
Page 253: ...16 Fuji Electric 16 1 PLC Connection 16 2 Temperature Controller Servo Inverter Connection...
Page 357: ...16 104 16 Fuji Electric Please use this page freely...
Page 358: ...17 1 Temperature Controller Servo Inverter 17 Gammaflux...
Page 364: ...17 6 17 Gammaflux Please use this page freely...
Page 365: ...18 GE Fanuc 18 1 PLC Connection...
Page 380: ...19 1 PLC Connection 19 Hitachi...
Page 394: ...19 14 19 Hitachi Please use this page freely...
Page 423: ...20 28 20 Hitachi Industrial Equipment Systems Please use this page freely...