Maintenance
M
aintenance
General Requirements
Operating Temperature Range: 41°F to 104°F (5 to 40°C)
Storage Temperature Range: -4°F to 158°F (-20 to 70°C)
Ambient Humidity: 20% – 95% relative humidity, non-condensing
Altitude: 0-7000 ft.
e
lectricity
r
eQUireMentS
All Machines Require:
AC input power is three phase Delta or Wye power, except that the power
source must be grounded (e.g. leg or center leg for delta, neutral for Wye)
Frequency range of 47-66 Hz
Line voltage that does not fluctuate more than ± 10%
Harmonic distortion not to exceed 10% of the total RMS voltage
20-15 HP System
(Standard VF and 10K, EC300, EC400)
195-260V Voltage
54-488V High-Voltage
Power Supply 1
50 AMP
25 AMP
Haas Circuit Breaker
40 AMP
20 AMP
If service run from elec.
panel is less than 100’ use:
8 GA. WIRE
12 GA. WIRE
If service run from elec.
panel is more than 100’ use:
6 GA. WIRE
10 GA. WIRE
40-30 HP System
(50 Taper, 40 Taper HT 10K, VF Super Speed, EC-300, EC-400
12K, VM)
195-260V Voltage
354-488V High-Voltage2
Power Supply1
100 AMP
50 AMP
Haas Circuit Breaker
80 AMP
40 AMP
If service run from elec.
panel is less than 100’ use:
4 GA. WIRE
8 GA. WIRE
If service run from elec.
panel is more than 100’
use:
2 GA. WIRE
6 GA. WIRE
40-30 HP System
(VS 1/3, HS 3-7 incl R models)
195-260V Voltage
Power Supply
125 AMP
Haas Circuit Breaker
100 AMP
If service run from elec. panel is
less than 100’ use:
2 GA. WIRE
If service run from elec. panel is
more than 100’ use:
0 GA. WIRE
Summary of Contents for 96-8000
Page 15: ...6 96 8000 Rev AC May 2010 Mill Warning Decals ...
Page 16: ...7 96 8000 Rev AC May 2010 Safety Lathe Warning Decals ...
Page 41: ...32 96 8000 Rev AC May 2010 ...
Page 93: ...84 96 8000 Rev AC May 2010 ...
Page 129: ...120 96 8000 Rev AC May 2010 ...
Page 133: ...124 96 8000 Rev AC May 2010 ...
Page 268: ......
Page 269: ......