WARNING! A separate earth ground wire of the same conductor size
as the input power is required to be connected to the chassis of the
machine. This ground wire is required for operator safety and for
proper operation. This ground must be supplied from the main plant
ground at the service entrance, and should be routed in the same
conduit as the input power to the machine. A local cold water pipe or
ground rod adjacent to the machine cannot be used for this purpose.
Input power to the machine must be grounded. For wye power, the neutral
must be grounded. For delta power, a central leg ground or one leg ground
should be used. The machine will not function properly on ungrounded power.
(This is not a factor with the External 480V Option.)
The rated horsepower of the machine may not be achieved if the imbalance of
the incoming voltage is beyond an acceptable limit. The machine may function
properly, yet may not deliver the advertised power. This is noticed more often
when using phase converters. A phase converter should only be used if all
other methods cannot be used.
The maximum leg-to-leg or leg-to-ground voltage should not exceed 260 volts,
or 504 volts for high-voltage machines with the Internal High Voltage Option.
1 The current requirements shown in the table reflect the circuit breaker size
internal to the machine. This breaker has an extremely slow trip time. It may be
necessary to size the external service breaker up by 20-25%, as indicated by
“power supply”, for proper operation.
2 The high-voltage requirements shown reflect the Internal 400V configuration
which is standard on European machines. Domestic and all other users must
use the External 480V option.
a
ir
r
eQUireMentS
The mill requires a minimum of 100 psi at the input to the pressure regulator
on the back of the machine. A volume of 4 scfm (9scfm for EC and HS mills) is
also necessary. This should be supplied by at least a two-horsepower com
-
pressor, with a minimum 20-gallon tank, that turns on when the pressure drops
to 100 psi.
Note: Add 2 scfm to the minimum air requirements (below) if the operator will
be using the air nozzle during pneumatic operations.
Machine Type
Main Air Regulator
Input Airline Hose Size
EC-300
85 psi
1/2" I.D.
EC-400
85 psi
1/2" I.D.
EC-1600
85 psi
1/2" I.D.
HS 3/4/6/7 incl R models
85 psi
1/2" I.D.
VF-1 - VF-11 (40Taper), VM
85 psi
3/8" I.D.
VF-5 - VF-11 (50 Taper)
85 psi
1/2" I.D.
VR Series
85 psi
1/2" I.D.
VS 1/3
85 psi
1/2" I.D.
Summary of Contents for 96-8000
Page 15: ...6 96 8000 Rev AC May 2010 Mill Warning Decals ...
Page 16: ...7 96 8000 Rev AC May 2010 Safety Lathe Warning Decals ...
Page 41: ...32 96 8000 Rev AC May 2010 ...
Page 93: ...84 96 8000 Rev AC May 2010 ...
Page 129: ...120 96 8000 Rev AC May 2010 ...
Page 133: ...124 96 8000 Rev AC May 2010 ...
Page 268: ......
Page 269: ......