6-20
Installing SATA M.2 SSDs
Guidelines
An M.2 transfer module is required to install SATA M.2 SSDs.
If you are installing two SATA M.2 SSDs, install two SATA M.2 SSDs of the same model to ensure
high availability.
As a best practice, use SATA M.2 SSDs to install the operating system.
The installation procedure is the same for SATA M.2 SSDs on both sides of the M.2 transfer module.
Procedure
1.
Power off the server. For more information, see "
2.
Remove the server from the rack. For more information, see "
Removing the server from a rack
."
3.
Remove the access panel. For more information, see "
."
4.
Remove the chassis air baffle. For more information, see "
5.
Insert the SSD into a socket on the M.2 transfer module, as shown in
the screw supplied with the transfer module to secure the SSD into place.
CAUTION:
If you are installing only one SATA M.2 SSD, install it in the socket on top of the transfer module,
as shown in
.
Figure 6-29 Installing a SATA M.2 SSD on the M.2 transfer module
6.
Align the screw holes on the M.2 transfer module with the threaded studs on the system board,
and insert the transfer module onto the system board. Then, use screws to secure the transfer
module into place, as shown in