——Parameter“Minimum time in fan speed [0…65535]*s”
It is used to define the stay time from current speed to higher or lower;it’s the minimum time of fan speed
switching.
Only when the stay time is over,can we switch the fan speed.
If the current speed is running long enough,the fan speed can be switched instantly.Options:0…65535
0:stands for no minimum time in fan speed switching,but the delay time during the speed switching should
be taken into consideration.
Note:
the stay time in this parameter can only be enabled at the auto mode.
The minimum running time should be taken into consideration at every fan speed(including off) under the
auto mode.
For example,when the current speed is at low while the target speed is high,the speed will be increasing
gradually from low to medium and then finally to high.
And the speed will be switched only after the minimum time is over.The delay time for speed switching
should also be taken into account.
6.5 Parameter Setting Window“Controller-General”
This is the general parameter setting for coil part of HVAC.
The parameters for fan and coil are separate.If the panel is used to control the Fan Coil unit,both fan and coil
parameter should be taken into consideration to get the best control effect.
Fig. 6.5_1 “Controller-General”parameter setting window