K-BUS
KNX/EIB 3.5/5.0/10.1 inch Touch Panel Plus
78
○
R
7.2 Communication object“General sensor”
Fig.7.2 “General sensor”communication object
No.
Function
Name
Data Type Flags
DPT
365
Actual temperature
Internal sensor
2Byte
C,R,T
9.001 temperature
The communication object is used to send the temperature value of internal sensor to the bus.The
value ranges:-50~99.8
℃
366
Temperature
External sensor
2Byte
C,W,T,U
9.001 temperature
The communication object is used to send the temperature value which is sent from the bus.The
value ranges:-50~99.8
℃
367
AQI
External sensor
2byte
C,W,T,U
7.001 pulses
The communication object is used to receive the AQI value from the bus and update it to the
panel.The value ranges:0~500
Note:
Currently the object is reserved.
368
PM2.5
External sensor
2byte
C,W,T,U
7.001 pulses
The communication object is used to receive the PM2.5 value from the bus and update it to the
panel.Unit is ug/m
3.
The value ranges:0~999ug/m
3
Note:
Currently the object is reserved.
369
PM10
External sensor
2byte
C,W,T,U
7.001 pulses
The communication object is used to receive the PM10 value from the bus and update it to the
panel.Unit is ug/m
3.
The value ranges:0~999ug/m
3
Note:
Currently the object is reserved.
370
Humidity
External sensor
2byte
C,W,T,U
9.007 humidity
The communication object is used to receive the humidity value from humidity sensor in the bus.
The value ranges:0~100%
Note:
Currently the object is reserved.
371
VOC
External sensor
2byte
C,W,T,U
The communication object is used to receive the VOC value from the bus and update it to the
panel.Unit is mg/m
3.
The value ranges:0~9.99mg/m
3
Note:
Currently the object is reserved.
372
CO2
External sensor
2byte
C,W,T,U
9.008
DPT_Value_AirQuality
The communication object is used to receive the CO2 value from the bus and update it to the
panel.Unit is ppm The value ranges:0~4000ppm.
Note:
Currently the object is reserved.