7.6.3 Communication Object for “Threshold comparator”
Figure 7.6_3“Logic function_Threshold comparator”Communication Object
No.
Function
Communication
Object Name
Type
Attribute
DPT
423
Threshold value input
1
st
/.../8
th
Logic
4bit
1byte
2byte
4byte
C,W, U
3.007 DPT_Dimming control/
5.010 DPT_counter pulses/
7.001 DPT_pulses/
12.001 DPT_counter pulses
This communication object is used to enter the threshold.
431
Logic result
1
st
/.../8
th
Logic
1bit
C,T
1.002 DPT_boolean
This communication object is used to send logical operation results. That is, the value that should be sent after the
object input threshold is compared with the parameter setting threshold.
Form 7.6_3“Logic function_Threshold comparator”Communication Object Form
7.6.4 Communication Object for “Format convert”
"2x1bit --> 1x2bit" function: converts 2 1bit values into a 2bit value, eg, Input bit1=1, bit0=0--> Output 2bit=2
"8x1bit --> 1x1byte" function: converts 8 1bit values into a 1byte value, such as Input bit2=1, bit1=1, bit0=1,
and other bits are 0-->Output 1byte=7.
"1x1byte --> 1x2byte" Function: Convert a 1 byte value to a 2 byte value, such as Input 1byte=125-->Output