K-BUS
KNX/EIB 3.5/5.0/10.1 inch Touch Panel Plus
87
○
R
which is used to send controlling message of AC mode - heating.
8
Status of control mode
Page x-AC
1byte
C,W,T,U
5.010 counter pulses
8
Cooling mode
Page x-AC
1bit
C,W,T,U
1.001 switch
1byte: The communication object will be visible when it’s in VRV AC mode & the mode type is
1byte, which is used to receive status feedback message of various modes of AC.
1bit: The communication object will be visible when it’s in VRV AC mode & the mode type is 1bit,
which is used to send controlling message of AC mode - cooling, which can also receive status
feedback.
9
Dry mode
Page x-AC
1bit
C,W,T,U
1.001 switch
The communication object will be visible when it’s in VRV AC mode & the mode type is 1bit, which is
used to send controlling message of AC mode - dehumidification, which can also receive status
feedback.
10
Fan mode
Page x-AC
1bit
C,W,T,U
1.001 switch
The communication object will be visible when it’s in VRV AC mode & the mode type is 1bit, which
is used to send controlling message of AC mode - air supply, which can also receive status feedback.
11
Fan speed
Page x-AC
1byte
C,T
5.010 counter pulses
11
Fan speed Auto
Page x-AC
1bit
C,W,T,U
1.001 switch
1byte:
The communication object will be visible when it’s in VRV AC mode & the mode type of wind
speed is 1byte, which is used to send controlling message of different level of wind speed.
1bit:
The communication object will be visible when it’s in VRV AC mode & the mode type of wind
speed is 1bit, which is used to send controlling message of wind speed - automatic, which can also
receive status feedback.
12
Status of Fan speed
Page x-AC
1byte
C,W,T,U
5.010 counter pulses
12
Fan speed low
Page x-AC
1bit
C,W,T,U
1.001 switch
1byte:
The communication object will be visible when it’s in VRV AC mode & the mode type of wind
speed is 1byte, which is used to receive of status feedback message of different level of wind speed.
1bit:
The communication object will be visible when it’s in VRV AC mode & the mode type of wind
speed is 1bit, which is used to send controlling message of wind speed - low gears, which can also
receive status feedback.
13
Fan speed medium
Page x-AC
1bit
C,W,T,U
1.001 switch
The communication object will be visible when it’s in VRV AC mode & the mode type of wind speed
is 1bit, which is used to send controlling message of wind speed - middle gears, which can also receive
status feedback.
14
Fan speed high
Page x-AC
1bit
C,W,T,U
1.001 switch
The communication object will be visible when it’s in VRV AC mode & the mode type of wind speed
is 1bit, which is used to send controlling message of wind speed - high gears, which can also receive
status feedback.
15
Temperature setpoint
Page x-AC
2byte
1byte
C,W,T,U
9.001 temperature
No-DPT
The communication object will be visible when it’s in VRV AC mode, which is used to send and
receive set temperature of AC.
Note: Object type is set by parameter, 2byte is suitable for KNX standard, 1byte is