current modes.
When the set temperature is for definite adjustment, the communication object is used for temperature set
value of modifying current room operation mode.
8
Switch heating/cooling
mode
Page x-HVAC Input
1bit
C,W,U
1.100
cooling/heating
The communication object is used to receive status feedback of heating and cooling from the BUS. The
touch panel will update icon display according to the received message value. Message value:
1——Heating
0——Cooling
9
HVAC mode
Comfort mode
Page x-HVAC Input
1byte
1bit
C,W
20.102 DPT_HVAC Mode
1.001 switch
10
Night mode
Page x-HVAC Input
1bit
C,W
1.001 switch
11
Frost/heat protection mode
Page x-HVAC Input
1bit
C,W
1.001 switch
12
Standby mode
Page x-HVAC Input
1bit
C,W
1.001 switch
Room operation mode can receive status feedback via 4 1bit object(object 9.10.11.12) or1 1byte
object(HVAC mode).
When it’s 1bit
:
object 9
:
comfort mode
,
object 10
:
night mode
,
object 11
:
protection mode
,
object 12
:
standby mode.
When the object receives message 1, corresponding mode will be activated, and the mode display status
will also update to relative mode on the panel.
When it’s 1byte: the relation between input value and operation mode is as following:no:0: unused
1: Comfort mode
2: Standby mode
3: Night mode
4: Protection mode
5-255: Unused
13
Fan speed
Fan speed low
Page x-HVAC Input
1byte
1bit
C,W,T,U
5.010 counter pulses
1.001 switch
14
Fan speed medium
Page x-HVAC Input
1bit
C,W,T,U
1.001 switch
15
Fan speed high
Page x-HVAC Input
1bit
C,W,T,U
1.001 switch
Wind speed can receive status feedback via object of 3 1bit(object 13.14.15) or object of 1 1byte.
When it’s 1bit
:
object 13
:
low speed
,
object 14
:
middle wind speed
,
object15
:
high speed.
When the object receives message 1, corresponding wind speed will be activated, and wind display status
will also update to relative wind speed on the panel.
When it’s 1byte
:
wind speed status value will be defined by parameter. When object receive appointed
value, and wind speed display status will also update to relative wind speed on the panel.
16
Fan automatic operation
Page x-HVAC Input
1bit
C,W,T,U
1.001 switch
The object is used to receive status feedback of automatic controlled wind speed.
17
Instantaceous setpoint
Page x-HVAC output
2byte
C,R,T
9.001 temperature