K-BUS
KNX/EIB 3.5/5.0/10.1 inch Touch Panel Plus
46
○
R
The following parameters are visible when the air conditioning mode is set to Split Infrared and are used
to set the values to be sent for each function command.
The actual telegram value is the entered value -1. The setting interface is shown as Figure 6.4_6.
Parameter “Command No. for power on (1~64, 0 is inactive)”
It is to set the telegram value of object “IR Split Unit Command” to be sent when AC is powered on. Available
Options: 0...64, 0=inactive
Other parameters settings which are similar to this parameter will not be described anymore. When the default
mode of the air conditioner is heating or cooling, the telegram value sent is same as the value of default
temperature (the temperature at this time is also limited to the maximum/minimum value).
The following three parameters is to set the initial icon status displayed on the touch panel when power on.
——Parameter “Default mode for power on”
To set initial mode displayed on the touch panel when power on. Options:
Heating
Cooling
Dry
Fan
——Parameter“Default setpoint for power on”
To set initial temperature displayed on the touch panel when power on. Options:
16
℃
...
32
℃
——Parameter “Default fan speed for power on”
To set the initial fan speed displayed on the touch panel when power on. Options:
Auto
Low
Medium
High
——Parameter “Default setpoint for heating/cooling”
To set the initial temperature displayed on the touch panel when switching to heating/cooling. Options:
16
℃
...
32
℃
The telegram value to be sent is same as the value of default temperature (the temperature at this time is
also limited by the maximum/minimum value).