6.4 Description of fault indications
If a fault occurs, the symbol
will be visible, an audible alarm will be given by the buzzer and the fault code will be written by means of
the 14-segment characters in the display. To see the kind of fault, if it is automatically reset and the code is not longer visible,
open the
fault log (see fig. 13). When you leave the fault log, the symbol
will disappear.
The last 20 faults are stored in the fault log as fault codes. The meaning of the fault codes are described in the table below:
Fault
code
Meaning
Displayed
text
Flashing
symbols
How to
reset fault
indications Description
Auto Man
F001
Phase sequence failure
F001
●
(Only three-phase pumps)
The phase sequence between control board and power
supply is wrong. See fig. 14.
F002
One phase missing
F002
●
●
(Only three-phase pumps)
One phase is missing.
F003
High liquid level
F003
●
●
The liquid level is high in relation to preset value.
F004
Sensor failure
SENSOR
-
●
●
Sensor signal out of range or lost.
F005
Overtemperature, pump 1
TEMP
●
●
Motor thermal switches connected to the controller will
stop pump in case of overheating.
F006
Overtemperature, pump 2
TEMP
●
●
Not relevant for Multilift M.
F007
Overcurrent, pump 1
F007
●
The pump is stopped if an overcurrent is measured for a
certain period of time (blockage protection).
F008
Overcurrent, pump 2
F008
●
Not relevant for Multilift M.
F009
Undercurrent, pump 1
F009
●
●
The pump is stopped if an undercurrent is measured for a
certain period of time (dry running protection).
F010
Undercurrent, pump 2
F010
●
●
Not relevant for Multilift M.
F011
Operating time exceeded,
pump 1
F011
●
●
The pump is stopped if normal operating time of the pump
is exceeded, e.g. due to venting problems of pump
housing, closed discharge valve (forgotten to open it after
service/maintenance), forgotten to switch back to
automatic mode, if ON-OFF-AUTO switch is set to "ON"
for service/maintenance. A subsequent emergency
operation starts and stops the pump automatically until
the controller gets a regular stop signal from the sensor.
The controller then switches back to normal operation.
F012
Operating time exceeded,
pump 2
F012
●
●
Not relevant for Multilift M.
F013
External fault
EXT
-
●
An external level switch can be connected to the
controller to give an alarm when basement outside the
lifting station is flooded by groundwater or water from
burst water pipe.
F014
Battery failure
BAT
-
●
●
The battery is empty and must be replaced.
F015
Relay or contactor does
not open, pump 1
RELAY
●
The pump receives a signal to stop, but does not react.
This situation is detected by current measurement.
F016
Relay or contactor does
not close, pump 1
RELAY
●
The pump receives a signal to start, but does not react.
This situation is detected by current measurement.
F017
Relay or contactor does
not open, pump 2
RELAY
●
Not relevant for Multilift M.
F018
Relay or contactor does
not close, pump 2
RELAY
●
Not relevant for Multilift M.
Summary of Contents for Multilift M Series
Page 1: ...GRUNDFOS INSTRUCTIONS Multilift M Installation and operating instructions...
Page 2: ...2...
Page 43: ...BG 43 7 LC 221 7 1 LC 221 11 11 LC 221 TM05 1807 3811 1234 AUTO 7 3 7 2...
Page 44: ...BG 44 7 4...
Page 48: ...BG 48 LED Man Auto LED ON OFF AUTO OFF LED ON OFF AUTO OFF 30 14 TM05 3455 0412...
Page 168: ...GR 168 6 LC 221 6 1 LC 221 11 11 LC 221 TM05 1807 3811 1234 AUTO 6 3 6 2...
Page 169: ...GR 169 6 4...
Page 292: ...KZ 292 5 2 2 9 1 6 1 Description of display 2 3 4 TM05 1805 3811 1 2 3 4 1 2 3 4 I 3 20 O...
Page 294: ...KZ 294 6 LC 221 6 1 Description of display LC 221 11 11 LC 221 TM05 1807 3811 1234 6 3 6 2...
Page 295: ...KZ 295 6 4...
Page 299: ...KZ 299 30 14 TM05 3455 0412...
Page 308: ...KZ 308 11 LC 221 1 a 5 2 LC 221 b 6 LC 221 c d F018 e f F005 10 4 Grundfos g...
Page 309: ...KZ 309 2 a 10 4 b F011 3 3 20 31 c F007 LC 221 8 4 LC 221 S3 12 10 4 3 a 24...
Page 420: ...UA 420 6 LC 221 6 1 LC 221 11 11 LC 221 TM05 1807 3811 1234 AUTO 6 3 6 2 Setup...
Page 421: ...UA 421 6 4...
Page 425: ...UA 425 Man Auto ON OFF AUTO OFF ON OFF AUTO 30 14 TM05 3455 0412...
Page 496: ...RU 496 8 LC 221 8 1 LC 221 11 11 LC 221 TM05 1807 3811 1234 8 3 8 2...
Page 497: ...RU 497 8 4...
Page 510: ...RU 510 13 LC 221 1 a 7 2 LC 221 b 8 LC 221 c d RELAY F018 e f SENSOR F005 12 4 Grundfos g...
Page 511: ...RU 511 2 a 12 4 b F011 3 3 20 31 c TEMP F007 LC 221 10 4 LC 221 S3 14 12 4 3 a 24...
Page 514: ...RU 514 15 1 2 Grundfos 16 24 Grundfos...
Page 699: ...CN 699 6 LC 221 6 1 LC 221 11 11 LC 221 TM05 1807 3811 1234 AUTO 6 3 6 2...
Page 700: ...CN 700 6 4...
Page 704: ...CN 704 Man Auto ON OFF AUTO OFF ON OFF AUTO OFF 30 14 TM05 3455 0412...
Page 716: ...Appendix 716 Appendix 1 Fig A Dimensional sketches M TM05 0440 1011...
Page 717: ...717...
Page 718: ...718...