Maintenance optimisation:
It is possible to generate a maintenance message that does not cause a boiler fault. This maintenance
message can occur after the 3 following counters reach set values:
• Time since last maintenance (or commissioning): set parameter 7044 to 12 months
• Hours of burner operation (parameter 7040)
• Number of start-ups (parameter 7042)
The last 2 parameters depend on the boiler room's hydraulic installation. It is advisable to use
at least parameter 7044 for annual maintenance.
• Menu
DHW tank
Adjust the rise
Temperature rise from initial setpoint (5020)
16 °C
• Menu
Domestic Hot Water
Configure an anti-legionella function
Anti-legionella function (1640)
- - -
Periodic legionella function (1641)
- - -
Anti-legionella temperature setpoint (1642)
- - -
Anti-legionella temperature setpoint (1645)
- - -
Anti-legionella function duration (1646)
- - -
Cascade optimisation:
The cascade can be optimised as required using the parameters in the
Cascade
menu. See the
NAVISTEM B3000 boiler controller manual for more details.