CONDENSINOX -
Installation, Use and Maintenance
Line
No.
Programming
Access
Default value
Customer setting
1663
Circulation setpoint
S
45 °C
1680
Optg mode changeover
S
Off
Consumer circuit 1
1859
Flow temp setp cons request
C
60 °C
1875
Excess heat draw
S
On
1878
With buffer
S
No
1880
With prim contr/system pump
S
No
Consumer circuit 2
1909
Flow temp setp cons request
C
60 °C
1925
Excess heat draw
S
On
1928
With buffer
S
No
1930
With prim contr/system pump
S
No
Consumer circuit 3
1959
Flow temp setp cons request
C
70 °C
1975
Excess heat draw
S
On
1978
With buffer
S
No
1980
With prim contr/system pump
S
No
Swimming pool
2055
Setpoint solar heating
S
26 °C
2056
Setpoint source heating
S
22 °C
2065
Charging priority solar
S
Priority 3
2080
With solar integration
S
Yes
Boiler
2203
Release below outside temp
S
--- °C
2208
Full charging buffer
S
Off
2210
Setpoint min
S
8 °C
2212
Setpoint max
S
83 °C
2214
Setpoint manual control
E
60 °C
2217
Setpoint frost protection
S
7 °C
2243
Burner off time min
S
5 min
2245
SD burner off time
S
6 °C
2250
Pump overrun time
S
5 min
2253
Pump overr time after DHW
S
1 min
2270
Return setpoint min
S
8 °C
2321
Starting speed
S
100 %
2322
Pump speed min
S
100 %
2323
Pump speed max
S
100 %
2330
Output nominal
S
40 kW :
50 kW
60 kW
80 kW :
100 kW :
40 kW
50 kW
60 kW
80 kW
100 kW
2331
Output basic stage
S
40 kW :
50 / 60 kW :
80 kW :
100 kW :
8 kW
12 kW
16 kW
20 kW
2334
Output at pump speed min
S
0 %
2335
Output at pump speed max
S
100 %
2441
Fan speed heating max
S
40 kW :
50 kW :
60 kW
80 kW :
100 kW :
6700
6910
7800
6400
7550