86 / 116
00CNO0192-E (U0627512)
CONDENSINOX -
Installation, Use and Maintenance
Diagram: CX13
page 7 / 8
F. OPTIMISING THE CONFIGURATION OF BOILER NO. 1 (SLAVE)
Adjusting the heating circuits (connected to the RVS 63):
Line No. Value
• Menu
Heating circuit 1
Adjust the comfort setpoint
Comfort setpoint (710)
- - -
Adjust the low setpoint
Low setpoint (712)
- - -
Adjust the heating curve slope
Curve slope (720)
- - -
• Menu
Heating circuit 2
Adjust the comfort setpoint
Comfort setpoint (1010)
- - -
Adjust the low setpoint
Low setpoint (1012)
- - -
Adjust the heating curve slope
Curve slope (1020)
- - -
Adjusting the timer program for the heating circuits (connected to the RVS 63):
• Menu
Heating circuit 1 timer program
Preselection
Preselection (500)
- - -
Adjust the programmed times
On/off phases (501…506)
- - -
• Menu
Heating circuit 2 timer program
Preselection
Preselection (520)
- - -
Adjust the programmed times
On/off phases (521…526)
- - -
• Switch the heating program for circuits 1 and 2 to automatic mode
Réglage de l'ECS (sur RVS 63) :
• Menu
Timer prog. 4/DHW
Adjust the programmed times
On/off phases (560…566)
- - -
• Menu
DHW
Adjust the low setpoint
Low setpoint (1612)
- - -
Release the DHW load according to the timer
program
Release (1620)
- - -
Adjust the frequency of the anti-legionella cycle
Anti-legionella function (1640)
- - -
According to the previous setting, adjust the
frequency or the day of the week
Periodic legion. funct.(1641)
- - -
Weekday legion. funct. (1620)
- - -