08.04.2021
77 / 116
CONDENSINOX -
Installation, Use and Maintenance
Diagram: CX12
page 4 / 6
Line No. Value
• Menu
Configuration
Start heating circuit 1
Heating circuit 1 (5710)
On
For heating circuit 1 to be effective, an actuator must be defined even if it is
not connected:
Configure pump Q2
Relay QX2 output (5891)
Pump HC1 Q2
Configure the isolation valve Q1.1
Relay QX3 output (5892)
Boiler pump Q1
Configure the cascade flow sensor B10:
Sensor input BX2 (5931)
Common flow sensor
B10
Configure input H1
H1 input function (5950)
Request consum
circuit 1
•
Configure as master of the cascade: Menu
LPB network
Device number
Appliance address (6600)
1
Segment number
Segment address (6601)
0
Configure the bus supply
Bus supply function (6604)
Automatic
Set the clock program
Clock operation (6640)
Master
• Menu
Heating circuit 1
Adjust the comfort setpoint
Comfort temperature setpoint (710) - - -
Set the curve slope
Heating curve slope (720) - - - (same as that
of the secondary
controller)
• Menu
Consumer circuit 1
Set the initial setpoint to use in the
event of a HC request
Cons. request initial setpoint (1859) 60°C (depends on
the Rubis setting)
• Set the heating program to permanent comfort