08.04.2021
69 / 116
CONDENSINOX -
Installation, Use and Maintenance
Line No. Value
• Menu
Heating circuit 2
Adjust the comfort setpoint
Comfort temperature setpoint (710) - - -
Set the curve slope
Heating curve slope (720) - - -
• Menu
Heating circuit 3
Adjust the comfort setpoint
Comfort temperature setpoint (710) - - -
Set the curve slope
Heating curve slope (720) - - -
• Set the heating program to permanent comfort
• Menu
Domestic Hot Water
Adjust the comfort setpoint
Comfort setpoint (1610) 55°C
Set the DHW release program
DHW release (1620) 24h/24
• Activate the DHR program
On boiler no. 2: slave
•
Configure as slave in the cascade: Menu
LPB network
Device number
Appliance address (6600)
2
Segment number
Segment address (6601)
0
Configure the bus supply
Bus supply function (6604)
Automatic
Set the clock program
Clock operation (6640)
Slave without
adjustment
• Menu
Configuration
Configure the isolation valve Q1.2
Relay QX3 output (5892)
Boiler pump Q1
Start heating circuit 1
Heating circuit 1 (5710)
On
Configure the direct circuit pump Q2
Relay QX2 output (5891)
Pump HC1 Q2
• Menu
Heating circuit 1
Adjust the comfort setpoint
Comfort temperature setpoint (710)
- - -
Set the curve slope
Heating curve slope (720)
- - -
Set the minimum starting temperature
Heating curve slope (740)
60°C (adjust
according to
low-level setting)
• Set the heating program to permanent comfort
Diagram: CX11
page 6 / 10