On boiler no. 3: slave
Line No. Value
•
Configure as slave in the cascade: Menu
LPB network
Device number
Appliance address (6600)
3
Segment number
Segment address (6601)
0
Configure the bus supply
Bus supply function (6604)
Automatic
Set the clock program
Clock operation (6640)
Slave without
adjustment
• Menu
Configuration
Start heating circuit 1
Heating circuit 1 (5710)
On
Configure the extension module
Extension module 1 function (6020)
Heating circuit 2
Configure the isolation valve Q1.3
Relay QX3 output (5892)
Boiler pump Q1
• Menu
Heating circuit 1
Adjust the comfort setpoint
Comfort temperature setpoint (710)
- - -
Set the curve slope
Heating curve slope (720)
- - -
• Set the heating program to permanent comfort
E. ELECTRICAL AND HYDRAULIC VALIDATION
On boiler no. 1: master
• Menu
Cascade troubleshooting
Confirm that all the boilers are present in the cascade
General status 1 (8100)
Released/not
released
General status 2 (8101)
Released/not
released
...............................
• Menu
Input/output test
Check the outputs
Alarm relay
Relay test (7700)
Relay QX1 output
Isolation valve Q1.1
Relay test (7700)
Relay QX3 output
DHW pump
Relay test (7700)
Relay QX2 output
All extension module relays
Relay test (7700)
Relay output QX2…
module…
Reset the outputs
Relay test (7700)
No test