78 / 116
00CNO0192-E (U0627512)
CONDENSINOX -
Installation, Use and Maintenance
On boiler(s) no. 2 (and above): slave
Line No. Value
• Menu
Configuration
For DHW to be effective, an actuator must be defined even if it is not
connected:
Configure the DHW pump Q3
Relay QX2 output (5891) DHW pump/valve
Q3
Configure the isolation valve Q1.2
Relay QX3 output (5892) Boiler pump Q1
•
Configure as slave in the cascade: Menu
LPB network
Device number
Appliance address (6600)
2 (or above for
the other slaves)
Segment number
Segment address (6601)
0
Configure the bus supply
Bus supply function (6604)
Automatic
Set the clock program
Clock operation (6640)
Slave without
adjustment
• Connect the bus between the boilers ( take care to respect the polarity).
•
Switch the slave boiler(s) off and on again. If communication is established properly, the clock is
updated correctly.
• Menu
Domestic Hot Water
Adjust the comfort setpoint
Comfort setpoint (1610) 55°C
Set the DHW release program
DHW release (1620) 24h/24
• Activate the DHR program
E. ELECTRICAL AND HYDRAULIC VALIDATION
On boiler no. 1: master
• Menu
Cascade troubleshooting
Confirm that all the boilers are present in the cascade
General status 1 (8100)
Released/not
released
General status 2 (8101)
Released/not
released
...............................
Diagram: CX12
page 5 / 6