ATTENTION:
To avoid any deterioration of the boiler, the CO
2
values measured
must be in conformity with the below table:
Models
Gas valve
Gas
Pre-setting/G20
CO
2
Pmax
CO
2
Pmin
40
GB-WND
055
D01 S20
G20
--
8.9 - 9.1
8.4 - 8.6
G25 set up for
G20 *
--
6.9 - 7.1
6.4 - 6.6
G25
Unscrew R1 (+ direction) 1.5-2 turns 8.7 - 8.9
8.0 - 8.2
G31
Screw R1 (- direction) 2-2.25 turns
+ screw R2 (+ direction) 1.25–1.5
turns
11.2 - 11.4 11.0 - 11.2
50
GB-WND
055
D01 S20
G20
--
8.9 - 9.1
8.4 - 8.6
60
GB-WND
055
D01 S20
G20
--
8.9 - 9.1
8.4 - 8.6
G25 set up for
G20 *
--
6.9 - 7.1
6.4 - 6.6
G25
Unscrew R1 (+ direction) 1.5-2
turns
8.6 - 8.8
8.1 - 8.3
G31
Screw R1 (- direction) 2-2.25 turns
+ screw R2 (+ direction) 1 turn
11.2 - 11.4 11.0 - 11.2
80
GB-WND
057
D01 S20
G20
--
8.7 - 8.9
8.4 - 8.6
G25 set up for
G20 *
--
6.8 - 7.0
6.7 - 6.9
G25
Unscrew R1 (+ direction) 2 turns
8.6 - 8.8
8.0 - 8.4
G31
Screw R1 (- direction) 2 turns
+ screw R2 (+ direction) 3 turns
9.8 - 10.0
9.4 - 9.7
100
GB-WND
057
D01 S20
G20
--
8.7 - 8.9
8.4 - 8.6
G25 set up for
G20 *
--
6.9 - 7.1
6.5 - 6.7
G25
Unscrew R1 (+ direction) 2.5-3 turns 8.6 - 8.8
8.4 - 8.6
G31
Screw R1 (- direction) 2 turns
+ screw R2 (+ direction) 1.5-2 turns 9.6 - 9.8
9.0 - 9.2
* G25 set up for G20: gas category
I
2E(S)
or
I
2E(R)