24 / 116
00CNO0192-E (U0627512)
CONDENSINOX -
Installation, Use and Maintenance
When calculating the duct length, take the following rules into account:
- 90° bend = 1 m of straight duct
- 45° bend = 0.5 m of straight duct
For the exhaust duct, respect a minimum slope of 3% towards the boiler in
horizontal sections.
To ease fitting coat the joints with liquid soap or an appropriate grease.
4.4.6.
C43 or C83 collective air vent connection
IMPORTANT:
For these connection types, consult us.
4.4.6.1.
Type C43
The boilers are connected to a common duct comprising two ducts connected
to a terminal that provides extraction of combustion products and combustion
air intake through orifices that are concentric or sufficiently close to operate
in similar wind conditions.
4.4.6.2.
Type C83
The boilers are connected to a common combustion product extraction duct.
The air intake ducts are connected to individual terminals taking air from
outside the building.