114 / 116
00CNO0192-E (U0627512)
CONDENSINOX -
Installation, Use and Maintenance
Line
No.
Programming
Access
Default value
Customer setting
8962
Common output setpoint
C
0 %
8980
Buffer temp 1
C
0 °C
8981
Buffer setpoint
C
0 °C
8982
Buffer temp 2
C
0 °C
8983
Buffer temp 3
C
0 °C
9005
Water pressure H1
C
0 bar
9006
Water pressure H2
C
0 bar
9009
Water pressure H3
C
0 bar
9031
Relay output QX1
C
Off
9032
Relay output QX2
C
Off
9033
Relay output QX3
C
Off
9034
Relay output QX4
C
Off
9050
Relay output QX21 module 1
C
Off
9051
Relay output QX22 module 1
C
Off
9052
Relay output QX23 module 1
C
Off
9053
Relay output QX21 module 2
C
Off
9054
Relay output QX22 module 2
C
Off
9055
Relay output QX23 module 2
C
Off
9056
Relay output QX21 module 3
C
Off
9057
Relay output QX22 module 3
C
Off
9058
Relay output QX23 module 3
C
Off
Burner control
9504
Required speed prepurging
S
40 kW :
50 / 60 kW :
80 kW :
100 kW :
4750
4550
4000
4000
9512
Required speed ignition
S
40 kW :
50 / 60 kW :
80 kW :
100 kW :
3950
4550
2300
2350
9524
Required speed LF
S
40 kW :
50 / 60 kW :
80 kW :
100 kW :
1600
1860
1500
1750
9529
Required speed HF
S
40 kW :
50 kW :
60 kW :
80 kW :
100 kW :
6700
6910
7800
6400
7550
9650
Chimney drying
S
Off
9651
Req speed chimney drying
S
200 tr/min
9652
Duration chimney drying
S
10 min