22 / 116
00CNO0192-E (U0627512)
CONDENSINOX -
Installation, Use and Maintenance
The Lmax lengths indicated exclude the terminal and 90° bend for the
C13 type and the terminal for the C33 type.
In addition, in calculating the duct lengths, take the following equivalences
into account:
- 90° bend = 1 m of straight duct
- 45° bend = 0.5 m of straight duct
The terminal location must respect the rules in section 4.2.3.
Use a minimum slope of 3% towards the boiler.
For type C13, drill a 150 mm hole in the wall for the 80/125 terminal and a
180 diameter hole for the 100/150 terminal. Seal the air vent terminal into the
wall with polyurethane foam to allow for removal if necessary.
To ease fitting coat the joints with liquid soap or an appropriate grease.
4.4.5. Connection to a C53 vent (G20 and G25 only)
C53 type connection:
Air intake and gas evacuation via 2 separate ducts.
IMPORTANT:
The use of the “Black vertical separate air vent” or "Ochre vertical
separate air vent" accessory is mandatory to connect a CONDENSINOX
boiler with a separate C53 vent.
The table below presents the accessories available for each boiler type.
CONDENSINOX
40
60
80
100
black C53
Code 040951
Code 040999
ochre C53
Code 040952
--
The approved ducts are Ubbink Rolux Separate Condensation 80/80 ducts
for 40 and 60 kW models and Ubbink Rolux Separate Condensation 100/100
for 80 and 100 kW models.
The location of exhaust and air terminals must comply with the rules in
section 4.2.3.